Toshiba TOSNIC-7000S User Manual

Page 47

Advertising
background image

- 46 -

6 F 3 H 1 0 0 1

Table 9.4 Fault (Trip)

# Item

LCD

Message

Indication

Description

1

52RT

52R TRIP

AC input circuit breaker #52R tripped.

2

72BT

72B TRIP

DC input circuit breaker #72B tripped.

3

71BF

DC FUSE BLW

DC Main circuit fuse blew.

4

86MU

MU FAULT1

An inverter or converted fuse blew.

5

WDCPU

WDCPU

An error occurred in the main control
microprocessor (CPU).

6

80PS

CONT. PS. ERR

The control power supply voltage fell.

7

80B1

BATT UV

Battery voltage is below discharged voltage.

8

5E

EPO SW ON

An emergency stop was specified by the external
contact input. (Option)

Table 9.5 Warning - 1 (Converter stop/Input power error)

# Item

LCD

Message

Indication

Description

1

27S

AC I/P UV

AC input voltage is low.

2

59S

AC I/P OV

AC input voltage is high.

3

95S

I/P FREQ. ERR

AC input frequency error.

Table 9.6 Warning - 2 (Stop and restart)

# Item

LCD

Message

Indication

Description

1

27I

AC O/P UV

AC output voltage is low.

2

59I

AC O/P OV

AC output voltage is high.

3

51L

AC O/P OL

Load is too high.

4 51I

AC

O/P

OC

Load

overcurrent.

5

51IO

INV OC

Inverter overcurrent.

6

76

DC OC

Excessive current in DC section of main circuit.

7

45

DC OV

Excessive voltage in DC section of main circuit.

8

51C

AC I/P OC

AC input overcurrent.

9

51CO

CONV OC

Converter overcurrent.

10

30MU

MU FAULT2

The converter and/or inverter gate voltage fell,
or the converter and/or inverter overheated.

11

26C

OVER TEMP

Temperature high in cubicle.

12

WDDSP

CONTROL ERR

An error occurred in the control microprocessor
(DSP).

Advertising