DESIGN GUIDELINES FOR 6041I INSERT INSTALLATION

INSTALLATION INTO A MASONRY FIREPLACE

When installing into a masonry fireplace, DO NOT

remove any bricks or masonry, with the following

exception: masonry or steel, including the damper

plate, may be removed from the smoke shelf and

adjacent damper frame, if necessary, to accommo-

date a chimney liner. Do this only if their removal

will not weaken the structure of the fireplace or

the chimney, and will not reduce protection for

combustibles to less than that required by national

building codes.

Installation must include a chimney liner (4” Pell

Vent “PL” Piping) that extends the full height of the

chimney and meets type HT requirements. The

liner must be securely attached to the insert and

the chimney top. The chimney must be sealed

either at the top or at the damper area with a non-

combustible plate to prevent room air passage to

chimney cavity.
Outside combustion air may be drawn through the

chimney top or through an existing ash cleanout.

INSTALLATION INTO A FACTORY-BUILT

(METAL) FIREPLACE

When installing into a zero clearance fireplace, The

firebox must accept the insert without modification

other than removing bolted or screwed together

pieces such as smoke shelf/deflectors, ash lips,

screen or door tracks, and damper assemblies.

These items must be re-installed if the insert is

removed and not replaced. The removal of any

part must not alter the integrity of the listed fire-

place in any way.
The factory built fireplace must be listed per UL

127. Installation must include a chimney liner (4”

Pell Vent “PL” Piping) that extends the full height

of the chimney and meets type HT requirements.

The liner must be securely attached to the insert

and the chimney top. The chimney must be sealed

either at the top or at the damper area with a non-

combustible plate to prevent room air passage to

chimney cavity.
For raised hearth installations, adjust the leveling

bolts under the front of the unit.

4” VENT IS MANDA-

TORY FOR INSERT

INSTALLATIONS.

4” VENT IS MANDA-

TORY FOR INSERT

INSTALLATIONS.