Clearances to combustibles 6041(tp)(hf) – United States Stove Company 6041TP User Manual

Page 8

Advertising
background image

8

USSC

CLEARANCES TO COMBUSTIBLES 6041(TP)(HF)

The heater must be installed with the following minimum clearances to side and back wall combustible materials.

NOTE: These are minimum clearances to combustible walls established by the testing lab.

PARALLEL - A - Sidewall to Top Edge of Unit

8 in./203mm

B - Sidewall to Flue

13 in./330mm

C - Backwall to Flue

3 in./75mm

D - Backwall to Unit

9 in./228mm

CORNER - E - Adjacent Wall to Flue

3 in./75mm

F - Adjacent Wall to Unit

4 in./100mm

BACK WALL

SIDE WALL

SIDE WALL

Backwall / Sidewall

Parallel

BACK WALL

Corner Installation

NOTE:

Allow sufficient space to remove the left and right side panels for maintenance purposes.

6”

min.

HEARTH PROTECTION

These clearances must be maintained.

6”

min.

6”

min.