Appendices – Univex 5100-02-IT User Manual

Page 31

Advertising
background image

Model 5100-02-IT Combustible Gas Sensor Module

Page: 29

8. APPENDICES

8.1

APPENDIX A: SPECIFICATIONS

Sensor:

Type:

Catalytic

Bead

Range:

0-100% LEL Combustible

Repeatability:

+/-1%

LEL

Response time:

< 12 sec to 60% full scale

Accuracy:

+/- 1% for 0-50% LEL range

+/- 2% for 51-100% LEL range

Sensor Life:

Typically >3 years

Output:

Display:

Fixed and Scrolling LED

Relays Option:

Trouble (SPDT Form C, 0.25 Amp@ 250VAC)

High Alarm, Low Alarm (5 Amp, 250VAC)

Signal Output:

Sentry Digital Bus

Analog 4-20 mA

3-wire

Non-Isolated

4-wire

Isolated

Serial RS-485 Modbus RTU

HART

Input:

Remote Alarm Reset:

Normally open digital input

Power:

Power consumption:

3 watts

Input voltage:

24 VDC nominal: 10-30VDC

RFI/EMI Protection:

EN50081-2, EN50082-2

Operating Range:

Ambient Temperature Range:

-40

o

to 176

o

F (-40

o

to 80

o

C)

Relative Humidity:

0-99% (noncondensing)

Enclosure:

Material – Aluminum:

Polyester powder-coated, sand-cast, copper-free aluminum

Material – Stainless Steel:

316 SS optional

Dimensions (H x W x D):

(A1 & A2) 6.9 x 5.7 x 3.9 in. (17.5 x 14.5 x 9.9 cm)

(S1 & S2) 7.5 x 5.0 x 4.4 in. (19 x 13 x 11 cm)

Weight:

(A1 & A2) 3.4 lb. (1.5 Kg)

(S1 & S2) 7.2 lb. (3.3 Kg)

Housing:

NEMA

4X/7

Hazardous Area Approval:

Explosion proof, Class I, Div. 1,

Groups B, C, D Class I, Zone 1,

Group IIC, IP66, IP65, NEMA 4X

II2 GD, Ex d IIC T6 = -40

o

C to 85

o

C

Approvals:

Factory Mutual (FM)

Performance:

FM Standard 6310 Performance Approval for

fixed-based Combustible Gas Detectors (ANSI/ISA – 12.13.01)

Hazardous

Locations:

FM Standards 3100, 3600, 3615, 3810

UL:

UL Standard 508A

SIL-2

Certified:

Certified by Lloyds Register (IEC 61508)

ABS:

Certificate of Compliance

CQST

Modbus:

Advertising