Unified Brands VENTILATION SYSTEMS User Manual

Page 17

Advertising
background image

14

The PAWS Control Panel is equipped with an

integral clock which can be used to

automatically operate the fan and wash cycles.

To set the time press "RETURN CLOCK" once.

The display will read "SET DAY AND TIME

SELECTED" and then change to "SET DAY

AND TIME" as well as the day and time. Press

"CHANGE CLEAR" and the day and time will

begin to flash. Press "DAY+" and/or "DAY-" to

set the correct day. Press "HOUR+" and/or

"HOUR-" to set the correct hour. Note if "AM"

or "PM" is displayed correctly. Press

"MINUTE+" and/or "MINUTE-" to set the

correct minutes. When you are satisfied that

the day and time are correctly displayed, press

"SAVE ENTER". The display changes to the

Normal Display. If no key is pressed for thirty

[30] seconds, the display will automatically

return to Normal Display.

b. Setting the PAWS

1. Single Wash Models [P-10__ & P-15__]

The wash can be programmed to run for up to

fifteen [15] minutes. It is followed by a recovery

period of from zero [0] minutes up to two [2]

hours. This period can be used in installations

which require that the fans automatically turn

on for a period of time after the wash cycle is

complete.

To review the PAWS, press "PAWS". The

display

will

indicate

"PAWS

MODE

SELECTED" for about three [3] seconds then

change to indicate the total PAWS duration

[wash and recovery periods] in hours and

minutes, and the duration of the wash period in

minutes. Press "NEXT" to display the duration

of the recovery period. Press "NEXT" to

display the duration of the fire delay cycle.

To change the duration of a segment, press

"NEXT" or "LAST" until the appropriate

segment is displayed, then press "CHANGE

CLEAR". When the display flashes, press

"MINUTE+" or "MINUTE-" until the duration is

displayed, then press "SAVE ENTER" to retain

that time. The total PAWS duration is

automatically updated.

To change the duration of an additional

segment, repeat the above procedure.

When all segments have been set, press

"RETURN CLOCK" to return to Normal Display.

If no key is pressed for thirty [30] seconds, the

panel will automatically return to Normal

Display.

2. Multi-Wash Models [P-20-__ & P-25-___]

As many as eight [8] hood sections can be

programmed to wash in sequence. [The total

number of washes and outputs is determined

prior to shipment and set at the factory]. Each

section can be programmed to wash for a

different period of time, up to fifteen [15]

minutes per section.

There are also up to eight [8] recovery periods

which can be programmed for different

durations from zero [0] minutes up to two [2]

hours per segment. The recovery periods can

be used to allow the water heater to recover

between wash segments in installations with a

limited hot water supply. It can also be used in

installations which require that the fans

automatically turn on for a period of time after

the final wash period.

To review PAWS, press "PAWS". The display

will indicate "PAWS MODE SELECTED" for

about three [3] seconds then change to indicate

the total PAWS duration [PAWS and recovery

periods] in hours and minutes, and the duration

of the first wash period in minutes. Press

"NEXT" to display the duration of the first

recovery period. Continue to press "NEXT" to

review the remaining wash and recovery

segments.

To change the duration of a wash or recovery

segment, press "NEXT" or "LAST" until the

appropriate segment is displayed, then press

"CHANGE CLEAR". When the display flashes,

press "MINUTE+" or "MINUTE-" until the

desired duration is displayed, then press

"SAVE ENTER" to retain that time. The total

PAWS duration is automatically updated.

To change additional segments, repeat the

above procedure.

When all segments have been set, press

"RETURN CLOCK" to return to Normal Display.

If no key is pressed for thirty [30] seconds, the

panel will automatically return to Normal

Display.

c. Setting The Fire Delay

To change the duration of the fire delay cycle

press "PAWS" to enter the PAWS Review

mode. Press "NEXT" to review all of the

PAWS segments. After the final PAWS

segment, press "NEXT" again and the display

will read "FIRE DELAY" and its duration. Press

"CHANGE CLEAR" and the display will begin to

flash. Press "MINUTE+" and/or "MINUTE-"

until the correct duration is displayed. Press

Advertising