h. Fan On During Recovery

The operator can choose to have the fan on

during PAWS recovery periods or remain off.

To have the fan come on during recovery, push

down the right side of switch number one of the

selector switch. To have the fan remain off

during recovery, push down the left side of

switch number one of the selector switch. [see

fig. 19]

i. Power Loss

In the event of a power loss the clock stops but

the PAWS and the Daily Event Schedule are

retained for up to six [6] months.

j. Last Command Indicator

In the Normal Display, the last digit of the top

row indicates the last command put into the

microprocessor.

The letters used are:

L = Power Loss

C = Clock or Program Change

P = Programmed Daily Event

Schedule Command

M = Manual fan or PAWS Command

H = Holiday in progress

LAST

DAY OF AM/PM COMMAND

WEEK TIME INDICATOR INDICATOR

FRI 06:45 PM M

FAN OFF/WASH OFF

PAWS NORMAL DISPLAY

fig. 17B

PAWS

Programming Keypad

k. Diagnostic LED Indicators

Because of the use of solid state relay circuits,

a conventional voltmeter may not give reliable

readings as regards to the operation of the

various inputs and outputs. To aid in

troubleshooting, diagnostic LED indicators

have been built into the left-hand side of the

Input/Output Board.

They are shown below.

D-1 Green

Illuminates when the number one wash

output is energized.

D-2 Green

Illuminates when the number two wash

output is energized.

D-3 Green

Illuminates when the number three wash

output is energized.

D-4 Green

Illuminates when the number four wash

output is energized.

D-5 Green

Illuminates when the number five wash

output is energized.

D-6 Green

Illuminates when the number six wash

output is energized.

D-7 Green

Illuminates when the number seven wash

output is energuzed.

D-8 Green

Illuminates when the number eight wash

output is energized.

D-9 Green

Illumintates when the detergent pump

output is energized.

D-10 Green

Illuminates when the PAWS Alarm Horn

output is energized.

D-11 Green

Illuminates when the ventilator fan

output is energized.

D-18 Red

Illuminates when the manual pull station

circuit is in the normal postion.

D-20 Green

Illuminates when the PAWS supervised

valve is open.

D-21 Red

Illumintes when the ventilator automatic fire

detection circuit is activated.

D-32 Red

Glows when the battery circuit is charging.

D-35 Red

Glows when the detergent level is low.