Installation Instructions

INSTALLATION REQUIREMENTS

FOR ALL AVTEC TAKU

VENTILATION HOODS




CANOPIES

Figure 1

Figure 2

HANGER BRACKET DETAIL

S.S. NUT & BOLT
BY OTHERS

HANGER ROD

HANGER ROD
NUT

Avtec hoods are provided with adjustable hanging brackets designed to receive 1/2”
threaded rod with a 1/2” nut and washer. Supporting rods must be connected to all factory
installed brackets. Recommended hanging height is 6’-6” above finished floor for
canopies. Low side wall ventilators should be installed directly upon a Avtec base or on a
rerated wall. If wall mounted, the bottom of the vent should be 36” above finished floor.

ALL AVTEC VENTILATION SYSTEMS MUST BE INSTALLED IN ACCOR-
DANCE WITH NFPA-96, REMOVAL OF SMOKE AND GREASE-LADEN
VAPORS FROM COMMERCIAL COOKING EQUIPMENT.

1. Check all local codes prior to installation. Special requirements may be necessary
depending upon building material construction.

2. Move crated hood to location of installation and very carefully uncrate hood.

3. Raise hood to proper hanging height.

4. Suspend hood from adequate roof supports using 1/2

"

threaded rods with nuts

and washers (See Fig. 1).

5. Level hood left to right and front to back.

6. Brackets are provided for hoods which are to be installed end to end or back to back.
Bolt brackets together using 3/8

"

bolt through holes provided (See Fig. 2).

7. Install C channel where the ends of the hood meet and install T moldings on front
face of hoods where they join. High temperature silicone can be used to install
channel and T moldings (See Fig. 3).

8. For make-up air hoods, the supply collar with built-in UL listed re damper and
air volume damper must be installed per instructions on collar.

9. Provide a removable service door in supply duct near re damper (See Fig. 4).

Figure 3

Figure 4

EXHAUST DUCT

INSULATED

PRE-DRILLED
HOLE, ACCEPTS
UP TO 1/2"ÿ ROD

PRE-DRILLED
HOLE, ACCEPTS
5/16" BOLT



HOOD

ANGLE

OF HOOD

NOTE: HOLES DRILLED THROUGH HOOD ANGLE BY

INSTALLER AFTER BRACKET ATTACHMENT

POINTS HAVE BEEN DETERMINED.

HOOD FACE



T-MOLDING








C-CHANNEL

SUPPLY DUCT

ACCESS

PANEL

FIRE DAMPER &

VOLUME CONTROL

DAMPER

FLUID WELD