Vanguard Heating POWERMAX PM200 User Manual

Page 18

Advertising
background image

16

MAINTENANCE


Lubrication
The water pump motor and the combustion air blower are permanently lubricated and
require no periodic maintenance. Auxiliary power vent motor (depending upon model)
may or may not need periodic adjustment or lubrication. Consult power vent manual.

Vent System
Check the vent system annually for damage and/or obstruction. Any deformation of the
vent system should be examined carefully to determine the cause of the deformation. The
problem MUST be rectified and any damage to the vent system MUST be repaired.

Check Burner Flame Condition
When the burner is operating properly, the flame will appear to have a light orange base
with a blue tint as you look through the burner observation window and across the burner
surface (fig.8 ). Inspect the burner periodically through the observation window. If areas
of the burner appear different or if the observation window is obscured, contact your
authorized service agency to have the burner inspected for proper operation. If the burner
is burning bright orange, red or white; it is too hot and will burn up igniters at an excessive
rate. Call factory and/or authorized service company to adjust air shutter.

Piping and General Condition
Periodically inspect the booster heater for any signs of water leakage, combustion by-
product leakage (soot, etc.), or wiring damage (electrical arcing, insulation damage).
Contact your authorized service agency to correct any damage or improper operation that
is discovered.

Check Air Filter
Regularly remove and inspect externally mounted air filter on the left side of booster. Filter
is easily cleaned with soap and water. A clogged filter will restrict flow of combustion air
which can lead to malfunction and internal damage. Damage caused by a blocked or
clogged filter is not covered under the warranty.

Advertising
This manual is related to the following products: