TROUBLE SHOOTING

CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.

PROBLEM

CAUSE

REMEDY

3. On-Off switch

powered, Unit does
not operate.

a. No power to heater.
b. Manual reset Hi-limit

tripped.

c. Vent fan interlock not

proving (if auxiliary
power vent or E-Z
Vent system) is
being used.

a. Check circuit breaker
b. Manually reset hi-

limit. Determine
cause. If hi-limit trips
again, call service.

c. Turn on fan, check

switch.

2. Unit energized,

blower not operating,
pump not operating,
burner(s) not on.

a. Fan defective.
b. Fan relay defective

or wiring
disconnected.

a. Check, replace fan.
b. Check, correct.
c. Check, clean air filter

3. Unit energized,

blower and pump
operating, burner(s)
are NOT on, ignition
control LED flashing.

a. Igniter Defective
b. Water flow switch

not proving.

c. Air flow/flue

blockage switch not
proving.

d. Control relay(s)

defective.

e. Control sensor(s)

defective.

f. Control

board

defective

g. Ignition control

defective.

h. Burner flame not

proving

a. Replace igniter or

call Service

b. Check, replace flow

switch.

c. Clear flue. Repair or

replace switch,

d. Call Service
e. Call Service
f. Call

Service

g. Call Service
h. Check, replace flame

sensor

4. Unit energized,

blower on, pump not
operating, burner(s)
NOT on.

a. Pump defective
b. Relay defective

a. Call Service
b. Call Service

Note: For service and/or parts call your authorized service agency or the
factory @ 1-800-624-4809