Hardware

Tank Gate Interface

12

Installation and Operations Manual

The choice of RS-232 or RS-485 is determined by the COM RS-232/RS-485 Selection Switch

SW2.

2.2.3.3 COM1 RS232/RS-485 Selection Switch (SW2)

Note COM1 is not available on the 8315 Tank Gate Interface

Switch SW2 determines whether RS-232 or RS485 is used. Note that the Hardware Handshaking

Switch SW1 affects the operation of COM1.

Figure 2-12: COM1 SW2 Switch

2.2.3.4 COM1 Hardware Handshaking Switch (SW1)

Note COM1 is not available on the 8315 Tank Gate Interface

For RS-232, there are two different settings. One setting is used if hardware handshaking (RTS/

CTS) is required. The other setting eliminates the need for hardware handshaking. Set the

Hardware Handshaking Switch to the ‘A’ position to use RTS/CTS when a modem or signal

converter is involved and requires RTS/CTS to operate. The RTS and CTS signals will be available

on terminal block J6. If the connection is direct using RS-232, jumper RTS to CTS by setting SW1

to the ‘B’ position.

Figure 2-13: COM1 SW1 Switch

EARTH

NEUTRAL

LINE

SURGE GND

A/TXD

B/RXD

GND

RTS

CTS

TXD

RXD

GND

+15V

+5V

GND

-15V

+

-

VFIELD

COM1

COM 0

AUX POWER

VFIELD=48V

VFIELD=24V

RESET

RS232

RS485

COM1

HARDWARE HANDSHAKING

A

B

RS232

RS485

COM1

SW2

EARTH

NEUTRAL

LINE

SURGE GND

A/TXD

B/RXD

GND

RTS

CTS

TXD

RXD

GND

+15V

+5V

GND

-15V

+

-

VFIELD

COM1

COM 0

AUX POWER

VFIELD=48V

VFIELD=24V

RESET

RS232

RS485

COM1

HARDWARE HANDSHAKING

A

B

HARDWARE HANDSHAKING

A

B

SW1