5.3.2

Application

The LJ1500 point provides an interface to L&J MCG1500 Servo Gauges. L&J Model 1500 Servo

Gauges are connected directly to a Model 8215 Tank Gauge Interface Module. The Model 8215

is automatically detected at sta8130 RTUp, and an LJSCAN point is automatically created to

manage the scanning task. The Module parameter determines which Model 8215 will be used.

The ID must match the unit address of the MCG 1500.

Maxtime

Specifies the maximum time (in secs) between automatic Change of

State data being sent to the Host in response to a Change of State

Request. Report must be set to either Low or High for the Value

parameter to be sent in response to a Change of State Request. A value

of 0 disables this option. Non-zero values cause responses to be sent

even if the value has not changed since the last message. The

maximum is 255 seconds. The default is 240.

Watchdog

Enables the watchdog task on the Motherboard. The watchdog task

monitors the LJ1500 point on the Model 8215 and verifies it is

scanning for gauges. If the Model 8215 fails, the 0x4000 and the

0x0010 bits of the PntStatus will be set to indicate the failure.

Dynamic Parameters

Function

Level

Floating point value representing the tank level (in feet).

Temp

Floating point value representing the tank temperature (in Fahrenheit).

PntStatus

Integer HEX value indicating status of point. Values are:
0x0002: Scan Timeout
0x0010: Gauge Not Responding
0x0020: Blown Transmit Fuse
0x0040: Parity Error
0x0080: Tankway Error
0x4000: Failure of the Model 8215. This bit is set if the Watchdog task

on the Motherboard determines that the Model 8215 has stopped

updating.

GaugeStatus

Byte value indicating status of the gauge.

AlarmTime

Time that alarm first occurred. The point is in alarm when the

PntStatus is non zero.

Elapse

Time of the last scan.

ScanTime

Time of the last good reading. A reading is considered good if it has no

parity or time-out error, and has passed the filter criteria.

Raw1

Raw data from gauge. Value reported as hexadecimal value.

Raw2

Raw data from gauge. Value reported as hexadecimal value.