Varec TankGate Interface 8315 Series User Manual
Page 23

8315 TGI
Hardware
Varec, Inc.
13
For RS-485, set the Hardware Handshaking Switch SW1 to the ‘A’ position. Refer to the following
table:.
Table 2-1:
Tank Gate Interface Communications Cable
The layout for the RS-232 cable between the PC and the Tank Gate Interface is shown in the
following illustrations.
Comm.
Physical
Layer
Hardware
Handshake
SW1
Setting
SW2
Setting
Notes
RS-232
No
A
UP (towards the
RS-232 side)
Use with a PC. Signals at terminal block J5 will
be RS-232
RS-232
Yes
B
UP (towards the
RS-232 side)
Use to communicate to systems that require
Request To Send (RTS) in order to transmit
(Modems, Radios, etc.)
RTS and CTS signals will be available at
terminal block J6
RS-485 Yes
A
DOWN
(towards
the RS-485
side)
Always SW1 set to the A position when using
RS-485..