Modbus Implementation

Tank Gauge Transmitter

46

Installation and Operations Manual

Table 9-1:

Modbus Functions

Note!

Exception: Because the ATT does not distinguish between inputs and outputs, function codes 01 and 02 as they apply
to bits, and function codes 03 and 04 as they apply to numeric values refer to the same data registers. For example,
either function code 03 or function 04 can be used to read the integer form of the true mass variable at data address
0053.

Table 9-2:

Modbus Configuration Information

Function

Code

Function

Information Type

Modbus Nomenclature

01

Read

Bits

Read output status

02

Read

Bits

Read input status

03

Read

Integer, Code, Status word,

Floating point

Read output registers

04

Read

Integer, Code, Status word,

Floating point

Read input registers

05

Write

Bits

Force single output status

06

Write

Integer, Code, Status word

Preset single register

08

n/a

Repeat of Loopback Message

Loopback test

15

Write

Bits

Force multiple outputs

16

Write

Integer, Code, Status word,

Floating point

Preset multiple registers

65

Read

Floating point

Read floating point registers

66

Write

Floating point

Write floating point registers

Configuration Item

Valid Entries

Modbus

Configurable

Model 1200

Configurable

Modbus Address

1 to 254

No

Yes

Maximum Integer Size

Whole number (0 to 65,534)

Yes

Yes

Integer Scaling Factors

Floating point number

Yes

Yes

Unit Selection

Coding list

Yes

Yes

Baud Rate

300, 600, 1200, 2400,

4800, 9600

No

Yes

Number of Stop Bits

1 or 2

No

Yes

Parity

Odd, Even, None

No

Yes