Check thermostat operation, Caution, Fan operation – White Rodgers 1F92W-71 User Manual

Page 7: Heating system, Cooling system

Advertising
background image

7

5.

Economizer — 1st stage cooling

6.

Automatic Changeover from Heat to Cool

The battery maintains the stored program in the event of
a power failure. When attached to the wall with 24vAC
power applied, the thermostat will function normally with-
out the battery. However, the program will be lost in the
event of power interruption or failure if the battery is not
installed. When power is restored, the thermostat will
automatically maintain a temperature of 64

°

F or a cooling

temperature of 82

°

F (factory preprogrammed) as needed.

CHECK THERMOSTAT OPERATION

When checking thermostat, option switch #4 for auto-
matic changeover must be in the OFF position. This will
allow temporary setting of heat set points above cool
settings. After system checkout, reset option switch to ON
position if automatic changeover is desired (see SET
OPTION SWITCHES
).

FAN OPERATION

1.

Turn on power to the system. If the auxiliary heat
source has a standing pilot, be sure to light it.

2.

Press

FAN

ON – AUTO

until FAN

is displayed. The blower

should begin to operate.

3.

Press

FAN

ON – AUTO

until FAN

is displayed. The blower

should stop operating within approximately one
minute.

HEATING SYSTEM

1.

Press

SYSTEM

HEAT-OFF-COOL-AUTO

until HEAT is displayed. (It should

already be displayed.)

2.

Press

to adjust thermostat to 99

°

F. All stages

of the heating system should come on within approxi-
mately five minutes. However, if the PUMP LED is
flashing, the compressor lockout feature is operating
(see Lockout Bypass Option to temporarily over-
ride the compressor lockout feature during testing).

LOCKOUT BYPASS OPTION

FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY. OPERATORS SHOULD NOT USE THIS
FEATURE DUE TO POSSIBILITY OF EQUIP-
MENT OR PROPERTY DAMAGE, OR PER-
SONAL INJURY.

DO NOT USE THE LOCKOUT BYPASS OP-
TION UNLESS THE COMPRESSOR OIL HEAT-
ERS HAVE BEEN OPERATIONAL FOR 6
HOURS AND THE SYSTEM HAS NOT BEEN
OPERATIONAL FOR AT LEAST 5 MINUTES.

COMPRESSOR LONG TERM CYCLE

PROTECTION

To protect the compressor from potential damage due
to temperature change of crankcase oil, this thermo-
stat has a built-in time delay of one hour less than the
power loss to the unit (up to 12 hours maximum
lockout). During this time, auxiliary heat will be used
when necessary to maintain setpoint temperature.
DO NOT attempt to override this delay feature before
crankcase temperature has stabilized (for example, if
power has been out for three hours, the compressor
should remain locked out for two hours).

COMPRESSOR SHORT TERM CYCLE

PROTECTION

This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature
while testing thermostat operation, simply press

ADV

PRGM

and

HOLD

TEMP

buttons at the same time at initial

startup.

NOTE

NOTE

CAUTION

!

CAUTION

!

ON

1

2

3

4

Switch #1 (see steps 1-4)
Switch #2 (see steps 1-4)
Switch #3
Switch #4 (see step 6)

ON

W1

Y2

When using economizer with
single stage heat pump, field
jumper W1 & Y2

ON

1

2

3

4

Switch #1 (see steps 1-4)
Switch #2 (see steps 1-4)
Switch #3 (see step 5)
Switch #4 ON

3.

Press

SYSTEM

HEAT-OFF-COOL-AUTO

so that EMER is displayed. Repeat

step 2.

4.

To program the thermostat, see OPERATION GUIDE.

COOLING SYSTEM

To prevent compressor and/or property damage,
if power to the compressor has been off or
interrupted for more than 1 hour and the outdoor
temperature is below 50

°

F, DO NOT operate the

system for at least the amount of time the com-
pressor was off! This will allow the compressor
heaters to warm the compressor oils to avoid
damage due to slugging.