White Rodgers 1F85-0422 User Manual

Applications, Specifications, Caution

Advertising
background image

1

Blue Universal Thermostat with

Automatic Heat/Cool Changeover Option

Single Stage, Multi-Stage or Heat Pump

Installation and Operating Instructions for Models:

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING
THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.

Save these instructions for future use!

APPLICATIONS

www.white-rodgers.com

www.emersonclimate.com

1F83-0422 Thermostat

Model

Programming Choices

1F85-0422

5/1/1 Day 5/2 Day

Non-Programmable

1F83-0422

Non-Programmable

THERMOSTAT APPLICATION GUIDE

Description
Heat Pump (No Aux. or Emergency Heat)

Yes

Heat Pump (with Aux. or Emergency Heat)

Yes

Systems with up to 2 Stages Heat, 2 Stages Cool

Yes

Heat Only Systems (with optional fan switch)

Yes

Millivolt Heat Only Systems – Floor or Wall Furnaces

Yes

Cool Only Systems

Yes

Gas or Oil Heat

Yes

Electric Furnace

Yes

Hydronic (Hot Water) Zone Heat – 2 Wires

Yes

Hydronic (Hot Water) Zone Heat – 3 Wires

Yes

PART NO. 37-7136A

1007

SPECIFICATIONS

Electrical Rating:

Battery Power .................................................... mV to 30 VAC, NEC Class II, 50/60 Hz or DC

Input-Hardwire ................................................... 20 to 30 VAC

Terminal Load ........................................................... 1.5 A per terminal, 2.5A maximum all terminals combined
Setpoint Range ......................................................... 45° to 90°F (7° to 32°C)
Differential (Single Stage) ......................................... Heat 0.6°F; Cool 1.2°F (adjustable)
Differential (Heat Pump) ........................................... Heat 1.2°F; Cool 1.2°F (adjustable)
Operating Ambient .................................................... 32° to +105°F (0° to +41°C)
Operating Humidity ................................................... 90% non-condensing max.
Shipping Temperature Range ................................... -4° to +150°F (-20° to +65°C)
Dimensions Thermostat ............................................ 3-7/8”H x 5-1/8”W x 1-1/4”D

ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this
product may replace a product that contains mercury.

Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For
proper disposal of a product containing mercury or a
sealed container of spilled mercury, place it in a suitable
shipping container. Refer to

www.white-rodgers.com for

location to send product containing mercury.

To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.

CAUTION

!

Index

Page

Installation

2

Wiring Connections

2

Thermostat Quick Reference

3

Installer Configuration Menu

4

Operating Your Thermostat

6

Programming

7

Troubleshooting

8

Advertising
This manual is related to the following products: