Quick wire, Quick wire ac power connection, Starting out – Watlow Electric Ramping and Profiling Microprocessor-Based Control SERIES 1500 User Manual

Page 7: 230vac, 115vac

Advertising
background image

Starting Out

WATLOW Series 1500 User's Manual

7

Starting Out, Chapter 1

Quick Wire

You may "power up " the Series 1500 with the following operational check-out. This
procedure also prepares you for the Sample Program in Chapter 2. Or, you may skip
this section and the sample program, and go directly to Chapter 3, Installation and
Wiring.

1.

Put the 1500 chassis back in its case. Then place the unit on a bench and
connect AC power lines and the jumper wires to the Power Supply terminal
strip. Use Figure 3 below.

2.

As soon as you apply power, the FUNCTION display will alternately flash "A1-
C1, A1-C1." Press the CLEAR key to clear the flashing A1. The display will
then flash another A-code.

When you apply power without sensor inputs on the Signal Conditioner
terminal strip, the Series 1500 will show a flashing "A-digit" in the FUNCTION
display. The digit is an alarm code The ACTUAL display will show four
steady dashes, "----," meaning "open sensor." These are normal displays for a
unit without sensors.

For 115VAC control operation,
install a jumper wire from Terminal
32 to Terminal 35, and a separate
jumper wire from Terminal 33 to
Terminal 36. Bring line power in to
Terminals 32 and 36. Connect the
line ground wire to Terminal 34.

Figure 3 -
Quick Wire AC
Power Connec-
tions

WARNING:
To avoid potential
electric shock use
National Electric
Code safety prac-
tices when wiring
and when connect-
ing this unit to a
power source and to
electrical sensors or
peripheral devices.

For 230VAC control operation,
install a jumper wire from Terminal
33 to Terminal 35. Bring line power
in to Terminals 32 and 36. Connect
the ground wire to Terminal 34.

230VAC

CHASSIS
GROUND

CHASSIS
GROUND

115VAC

L1

L1

L2

L2

CLEAR
Key

ACTUAL
Display

FUNCTION
Display