Step 9 – Westinghouse Teco MA7200 Plus User Manual

Page 10

Advertising
background image

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company

10

PRGM

DRIVE

DSPL

EDIT

ENTER

Sn – 01 -

key twice

Inverter Capacity

Flashing

To set the parameter Sn-24 = 0

Keypad Steps

Resulting Display

1 - Press the

2 - Press the

3 - Press the

key until display shows

4 - Press the

key

(VIN, 0 – 10 VDC)

key

An – 01 -

Freq. Cmd. 1

Sn – 24

Sn – 24 = 1

CMD. AIN

EDIT

ENTER

key to save.

5 - Press the

key

6 - Press the

Entry Accepted

2 Seconds

PRGM

DRIVE

7 - Press the

key to return to the main display.

Flashing

Sn – 24 = 0

CMD. VIN

Flashing

Sn – 24 = 0

External Input

CMD. VIN

Step 9

– Select Feedback Engineering Units (P1-01) and Scaling (P1-02)

•

Initially the display will read output frequency in (Hz) as the factory default and is set by
parameter (Cn-28=0). If (Cn-28) is changed to (=1), then the display will read out in (%). The
setting of (Cn-28) is only valid if (P1-01=0), which is the factory default. Other engineering units
may be selected by parameter setting (P1-01) as described on the following page.

•

In this step, the feedback engineering units that the system is controlling such as CPM in fan
applications or PSI in the case of pumps can be selected by parameter (P1-01). (See Appendix
A
for additional selections)
. The maximum value that the engineering units will be in any given
application is set by parameter (P1-02). These selections will now be displayed on the digital
operator.

Example: A pump application that has a feeedback transducer with a maximum value of
200 PSI i.e 200 PSI = 20mA or 10 Vdc, can be set as shown next.