Step 11 – s – Westinghouse Teco MA7200 Plus User Manual

Page 15

Advertising
background image

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company

15


Step 11 –
S

etting parameters acceleration (Bn-01) and deceleration (Bn-02)

times

Acceleration and Deceleration times as well as the PID control [(P) Proportional Gain

and/or the (I) Integral Time (see STEP 11) directly control the system dynamic response.
The longer the acceleration and deceleration time, the slower the system response, and the
shorter time, the faster the response. An excessive amount of time can result in sluggish
system performance while too short of a time may result in system instability.

The starting values suggested by this guide normally result in good system performance for
the majority of fan and pump applications. If the values need to be adjusted, caution
should be exercised, and the changes should be in small increments to avoid system
instability.

• Parameters

Bn-01 (Acceleration) and Bn-02 (Deceleration) are both set at the factory for

10.0 seconds. For fan and pump applications, the recommended starting values are 30
seconds.
To change these parameters, follow the keypad navigation procedure as shown
next.

PRGM

DRIVE

DSPL

Bn-01

key

Acc. Time 1

1 - Press the

2 - Press the

3 - Press the

key

key

An – 01 -

Freq. Cmd. 1

EDIT

ENTER

key to save.

5 - Press the

Entry Accepted

2 Seconds

Flashing

EDIT

ENTER

Flashing

Keypad Steps

Resulting Display

RESET

key 3 times; then the

Key twice

4 - Press the

Flashing

Bn-01 = 0010.0

Next set Bn-02 = 0030.0

To set parameter Bn-01 = 30.0 s

(Acceleration Time )

Acc. Time 1

Acc. Time 1

Bn-01 = 0030.0

Bn-01 = 0030.0

Acc. Time 1

Advertising