MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company

9


Step 8

– Select PID control (Sn-64), and Feedback input (Sn – 24) [4 – 20 mA

or 0 – 10 Vdc]

Before selecting the parameter(s), ensure the inverter is in the STOP mode.

To activate PID control parameter (Sn-64) must be set to =1.

The Feedback Input parameter (Sn –24) is set to = 1 (AIN, 4-20 mA), as factory default. To
select (VIN, 0-10 Vdc), (Sn-24) must be set to 0. (See Figs. 3a, 3b and 3c for feedback
connections)

To set the parameter(s), follow the navigation procedure as shown next.

key twice

Flashing

1 - Press the

2 - Press the

3 - Press the

key until display shows

4 - Press the

key

(Turn on PID control)

key

0

key to

.

5 - Press the

key

6 - Press the

2 Seconds

7 - Press the

key to return to the main display.

Flashing

1

Flashing

1