Field wiring, 2 — control supplement – Weil-McLain -230 User Manual

Page 4

Advertising
background image

Part number 550-100-029/0404

GAS

-

FIRED

WATER

BOILER

SERIES

2 — Control Supplement

4

Field wiring

1

ELECTRICAL SHOCK HAZARD —
For your safety, turn off electrical power
supply at service entrance panel before
making any electrical connections to avoid
possible electric shock hazard. Failure to
do so can cause severe personal injury or
death.

Wiring must be N.E.C. Class 1. If original
wiring as supplied with boiler must be
replaced, use only type 105 °C wire or
equivalent. Boiler must be electrically
grounded as required by National Electrical
Code ANSI/NFPA 70 – latest edition.

2. Provide and install a fused disconnect or service switch (15 amp. recommended)

as required by the code. (See Figure 2, item 2)

3. Boiler circulator is shipped loose. Wire Boiler circulator as shown for Figure 2,

item 3.

4. When connecting a DHW circulator, connect wiring to line voltage terminal

strip as shown for Figure 2, item 5.

5. Route all wires and conduits to the jacket openings specified in Figure 1.

Wiring a system circulator

1. To activate a system circulator when the Boiler circulator operates, add a circulator

relay and wire as shown in Figure 2.

2. You must install a relay as shown. DO NOT wire in parallel with the Boiler

circulator. See CAUTION in Figure 2.

Low voltage connections

1. Connect low voltage wiring to low voltage terminal strip (Figure 3, page 5,

item 1) as shown in Figure 3 and the boiler wiring diagram.

2. Route all low voltage wires through grommeted jacket opening to right of low

voltage terminal strip, as shown in Figure 1.

Thermostat

1. Connect Figure 3, item 2, room thermostat or end switch (isolated contact

only) between terminals 5 and 6.

2. Install thermostat on inside wall away from influences of drafts, hot or cold

water pipes, lighting fixtures, television, sunrays, or fireplaces.

3. Thermostat anticipator (if applicable):

a. If connected directly to boiler, set for 0.1 amps.
b. If connected to relays or other devices, set to match total electrical power

requirements of connected devices. See device manufacturers’ specifications
and thermostat instructions for details.

Outdoor temperature sensor

1. Connect outdoor temperature sensor (Figure 3, item 6) between terminals 1

and 2 to enable outdoor reset operation of the Ultra boiler. If fixed-temperature
operation is required, do not install outdoor sensor.

2. Mount sensor on exterior wall, shielded from direct sunlight or flow of heat or

cooling from other sources.

3. If desired, install a summer/winter switch (Figure 3, item 7) across terminals 1

and 2. When the switch is closed, the boiler (space heating) circulator is disabled.

4. Route sensor wires through the hole at the right of the electrical entrance (see

Figure 1).

DHW aquastat

1. Connect storage indirect water heater (DHW) aquastat (Figure 3, item 3) between

terminals 3 and 4.

Additional limits

1. Connect additional limit controls and interlocks between the terminals shown

in Figure 3.

2. Controls connected between terminals 6 and 7 (see Figure 3, item 4) will cause

a soft lockout (automatic reset). When limit(s) closes, boiler will resume normal
operation.

3. Controls connected between terminals 6 and 8 (see Figure 3, item 5) will cause

a hard lockout (manual reset). The boiler will only restart after the Ultra display
panel RESET switch is pressed.

Figure 1

Routing field wiring

Installation must comply with:

1. National Electrical Code and any other national, state,

provincial or local codes or regulations.

2. In Canada, CSA C22.1 Canadian Electrical Code Part 1,

and any local codes.

Line voltage connections

1. Connect 120 VAC power wiring to line voltage terminal

strip in left compartment of electrical entrance, as shown
in Figure 2, page 5, item 1.

Install field wiring before venting to allow
easier access to terminal strips.

Advertising
This manual is related to the following products: