Mounting the XADC and Panel Remotely

To mount the XADC and panel remotely:

1. Slide the panel into the mounting cutout (12 in. × 8 in. – 305 mm × 203 mm).

2. Fasten the panel to the mounting surface using 6 × #6 or #8 pan head, round

head or washer head screws suitable for mounting the panel onto
particleboard or wood.

3. Install the panel faceplate and tighten the center screw (do not overtighten as

this may cause stripping of the screw threads).

4. Install the DC fuse cover.

5. Follow the instructions in “Mounting the XADC” on page 15 to mount the

XADC.

DC Wire Size and Torque Values

Table 1 Torque Requirements

Connection

Torque Value

DC (+) Load Output Terminal

12 in-lbs (12-14 AWG)

DC (+) Battery Terminal Lug

30 in-lbs (2 AWG)
28 in-lbs (4-6 AWG)
25 in-lbs (8 AWG)
25 in-lbs (10-14 AWG)

DC (-) Ground Terminal Lug

30 in-lbs (2 AWG)
28 in-lbs (4-6 AWG)
25 in-lbs (8 AWG)
25 in-lbs (10-14 AWG)

DC (-) Ground Terminal Bus

35 in-lbs (4-6 AWG)
25 in-lbs (8 AWG)
20 in-lbs (10-14 AWG)

Line/Load Terminals

See Circuit Breaker

AC Neutral/Ground Terminal Bus(s) 35 in-lbs (4-6 AWG)

25 in-lbs (8 AWG)
20 in-lbs (10-14 AWG)

Ground Terminal

45 in-lbs (6 AWG)
40 in-lbs (8 AWG)
35 in-lbs (10-14 AWG)

Table 2 DC Wire Size (to battery bank)

Converter model

Recommended minimum
DC wire gauge

Recommended maximum 2-way
DC cable length

a

a.Run lengths over 20 ft. (610 cm) are not recommended. Using larger run lengths or smaller gauge wires than recom-
mended will result in decreased charge/load output performance as well as additional heating and interference effects.

XADC-40

8 AWG

20 ft (610 cm)

XADC-60

6 AWG

20 ft (610 cm)

XADC-80

4 AWG

20 ft (610 cm)