York SUNLINE 2000 D2CG 072 User Manual

Page 12

Advertising
background image

OUTDOOR

TEMPERATURE,

°

F

SUPERHEAT AT SCROLL COMPRESSOR SUCTION,

°

F, AIRFLOW = 400 CFM/TON

INDOOR WB TEMPERATURE,

°

F

55

57

59

61

63

65

67

69

71

73

75

65

25.6

26.8

28

29.2

30.4

31.6

32.8

33.3

33.9

34.4

34.9

70

20.1

21.7

23.3

24.9

26.5

28.1

29.6

30.6

31.5

32.4

33.4

75

14.6

16.6

18.5

20.5

22.5

24.5

26.5

27.8

29.1

30.5

31.8

80

9.0

11.4

13.8

16.2

18.5

20.9

23.3

25.0

26.8

28.5

30.3

85

-

6.3

9.0

11.8

14.6

17.4

20.1

22.3

24.4

26.6

28.7

90

-

-

6.7

9.1

11.4

13.8

16.2

18.9

21.7

24.4

27.1

95

-

-

-

6.3

8.3

10.3

12.3

15.6

18.9

22.2

25.6

100

-

-

-

5.3

6.8

8.4

10.0

13.4

16.8

20.2

23.6

105

-

-

-

-

5.4

6.5

7.7

11.2

14.7

18.2

21.7

110

-

-

-

-

-

-

5.4

9.0

12.6

16.2

19.8

115

-

-

-

-

-

-

-

6.8

10.5

14.1

17.8

TABLE 12 - SUPERHEAT CHARGING TABLE FOR MODEL 036

UNIT

SIZE

POWER

SUPPLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

SCROLL

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

18.0

11.4

6.2
5.0

105.0

90.0
45.0
36.0

1.3
1.3
0.8
0.8

5.3
5.3
3.1
3.1

29.1
20.9

11.7

10.2

45
30
15
15

45
30
15

-

048

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

24.4
14.1

7.1
5.6

140.0
105.0

55.0
44.0

1.3
1.3
0.8
0.8

8.6
5.2
2.6
2.0

40.4
24.1
12.3

9.9

60
35
15
15

60
35
15

-

060

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

28.9
16.0

8.0
6.4

165.0
125.0

67.0
50.0

1.3
1.3
0.8
0.8

8.6
6.0
3.0
2.4

46.0
27.3
13.8

11.2

70
40
20
15

70
40
20

-

072

208/230-3-60

460-3-60
575-3-60

187
414
518

253
504
630

20.3
10.2

8.2

146.0

73.0
58.4

1.3
0.8
0.8

7.3
3.7
2.8

34.0
17.3
13.9

50
25
20

50
25

-

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type.

TABLE 11 - ELECTRICAL DATA (BASIC UNIT)

w/Belt-Drive Blower Motor

UNIT

SIZE

POWER

SUPPLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

SCROLL

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

18.0

11.4

6.2
5.0

105.0

90.0
45.0
36.0

1.3
1.3
0.8
0.8

4.4
4.4
2.2
2.2

28.2
20.0
10.8

9.3

45
30
15
15

45
30
15

-

048

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

24.4
14.1

7.1
5.6

140.0
105.0

55.0
44.0

1.3
1.3
0.8
0.8

5.0
5.0
2.2
2.2

36.8
23.9

11.9

10.1

60
35
15
15

60
35
15

-

060

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

28.9
16.0

8.0
6.4

165.0
125.0

67.0
50.0

1.3
1.3
0.8
0.8

6.6
6.6
3.3
3.3

44.0
27.9
14.1
12.1

70
40
20
15

70
40
20

-

072

208/230-3-60

460-3-60
575-3-60

187
414
518

253
504
630

20.3
10.2

8.2

146.0

73.0
58.4

1.3
0.8
0.8

6.8
3.6
3.6

33.5
17.2
14.7

50
25
20

50
25

-

NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type.

w/Direct-Drive Blower Motor

TABLE 10 - ELECTRICAL DATA (BASIC UNIT)

530.18-N8Y

12

Unitary Products Group

Advertising
This manual is related to the following products: