York 036-21103-003 User Manual

Page 2

Advertising
background image

036-21103-003 Rev. A (0403)

2

Unitary Products Group

PHYSICAL AND ELECTRICAL DATA - 1 & 3 Phase

MODEL

H1RA018S78 H1RA024S78 H1RA030S78 H1RA036S78 H1RA036S50 H1RA048S50 H1RA060S50

Unit Supply Voltage

230 – 1 – 50

380/415 – 3 – 50

Normal Voltage Range

1

1. Rated in accordance with ARI Standard 110, utilization range “A”.

207 to 253

342 to 455

Minimum Circuit Ampacity

9.8

14.6

20.4

20.8

7.3

10.8

13.3

Max. Qvercurrent Device Amps

2

2. Dual element fuses or HACR circuit breaker.

15

25

35

35

15

15

20

Compressor Type

Recip

Recip

Recip

Recip

Recip

Recip

Recip

Compressor Amps

Rated Load

7.4

11.3

15.2

15.5

5.2

7.2

9.2

Locked Rotor

53

65

90

82

39

53

79

Crankcase Heater

No

No

No

No

No

No

No

Fan Motor Amps

Rated Load

.5

.5

1.8

1.8

.8

1.8

1.8

Fan Diameter Inches

18

18

18

18

18

22

22

Fan Motor

Rated HP

1/12

1/12

1/4

1/4

1/4

1/3

1/3

Nominal RPM

970

970

900

900

1,100

1,075

1,075

Nominal CFM

1,650

1,650

2,350

2,350

2,250

3,200

3,300

Coil

Face Area Sq. Ft.

8.00

8.00

9.15

9.15

9.15

15.72

23.58

Rows Deep

1

1

1

1

1

1

1

Fin / Inches

14

14

16

16

18

18

18

Liquid Line OD

3/8

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line OD

3/4

3/4

3/4

3/4

3/4

7/8

7/8

Unit Charge (Lbs. - Oz.)

3

3. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than

15 feet, refer to publication 035-15893-60*

3 - 13

3 - 14

3 - 15

4 - 11

4 - 11

7 - 10

9 - 12

Charge Per Foot, Oz.

0.66

0.66

0.68

0.68

0.68

0.70

0.70

Operating Weight Lbs.

118

123

135

137

137

206

228

UNIT

MODEL

H1RA

DIMENSIONS

(INCHES)

REFRIGERANT

CONNECTION

LINE SIZE

A

1

1. Including fan guard

B

C

Liquid

Vapor

018S78

17

35

23

3/8”

3/4”

024S78

17

35

23

030S78

19

35

23

036S78

19

35

23

036S50

19

35

23

048S50

27

37

27

7/8”

060S50

39

37

27

All dimensions are in inches. They are subject to
change without notice. Certified dimensions will be
provided upon request.

Advertising