17 electrical data - dh036, 048 & 060 direct drive, W/powered convenience outlet – York CSA DH 036 User Manual

Page 17

Advertising
background image

254597-YTG-B-0507

Unitary Products Group

17

TABLE 17: ELECTRICAL DATA - DH036, 048 & 060 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET

MODEL

TONNAGE

VOLTAGE

COMPRESSORS

OD FAN
MOTOR

FLA

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

FLA

ELECTRIC HEATER

MODEL NO.

HEATER

KW

HEATER

AMPS

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX. FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

DH036

208-3-60

13.1

110.0

2.3

8.0

10.0

None

--

--

36.7

45

2CE04510525

2

4.0

11.1

36.7

45

2CE04510725

2

5.6

15.5

41.9

45

2CE04511025

8.0

22.2

50.3

60

2CE04511525

11.9

33.0

63.8

70

2CE04512025

15.9

44.1

77.7

80

230-3-60

13.1

110.0

2.3

8.0

10.0

None

--

--

36.7

45

2CE04510525

2

5.3

12.7

38.4

45

2CE04510725

2

7.5

18.0

45.1

50

2CE04511025

10.6

25.5

54.4

60

2CE04511525

15.9

38.2

70.3

80

2CE04512025

21.2

51.0

86.2

90

DH048

208-3-60

13.1

110.0

2.3

10.6

10.0

None

--

--

39.3

50

2CE04510525

2

4.0

11.1

39.6

50

2CE04510725

2

5.6

15.5

45.2

50

2CE04511025

8.0

22.2

53.5

60

2CE04511525

11.9

33.0

67.0

70

2CE04512025

15.9

44.1

80.9

90

230-3-60

13.1

110.0

2.3

10.6

10.0

None

--

--

39.3

50

2CE04510525

2

5.3

12.7

41.7

50

2CE04510725

2

7.5

18.0

48.3

50

2CE04511025

10.6

25.5

57.6

60

2CE04511525

15.9

38.2

73.6

80

2CE04512025

21.2

51.0

89.5

90

DH060

208-3-60

16.0

137.0

2.3

10.6

10.0

None

--

--

42.9

50

2CE04510525

2

4.0

11.1

42.9

50

2CE04510725

2

5.6

15.5

45.2

50

2CE04511025

8.0

22.2

53.5

60

2CE04511525

11.9

33.0

67.0

70

2CE04512025

15.9

44.1

80.9

90

2CE04513025

22.2

61.6

102.8

110

230-3-60

16.0

137.0

2.3

10.6

10.0

None

--

--

42.9

50

2CE04510525

2

5.3

12.7

42.9

50

2CE04510725

2

7.5

18.0

48.3

50

2CE04511025

10.6

25.5

57.6

60

2CE04511525

15.9

38.2

73.6

80

2CE04512025

21.2

51.0

89.5

90

2CE04513025

29.6

71.2

114.8

125

1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block

accessories 2FB04700825 and 2FB04700846 are available for field installation.

Advertising