18 electrical data - dh036-060 belt drive, W/powered convenience outlet – York CSA DH 036 User Manual

Page 18

Advertising
background image

254597-YTG-B-0507

18

Unitary Products Group

TABLE 18: ELECTRICAL DATA - DH036-060 BELT DRIVE W/POWERED CONVENIENCE OUTLET

MODEL

TONNAGE

VOLTAGE

COMPRESSORS

OD FAN
MOTOR

FLA

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

FLA

ELECTRIC HEATER

MODEL NO.

HEATER

KW

HEATER

AMPS

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX. FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

DH036

(3.0)

208-3-60

13.1

110.0

2.3

5.2

10.0

None

--

--

33.9

45

2CE04510525

2

4.0

11.1

33.9

45

2CE04510725

2

5.6

15.5

38.4

45

2CE04511025

8.0

22.2

46.8

50

2CE04511525

11.9

33.0

60.3

70

2CE04512025

15.9

44.1

74.2

80

230-3-60

13.1

110.0

2.3

5.2

10.0

None

--

--

33.9

45

2CE04510525

2

5.3

12.7

34.9

45

2CE04510725

2

7.5

18.0

41.6

45

2CE04511025

10.6

25.5

50.9

60

2CE04511525

15.9

38.2

66.8

70

2CE04512025

21.2

51.0

82.7

90

460-3-60

6.7

54.0

1.3

2.6

5.0

None

--

--

17.3

20

2CE04510746

2

6.8

8.2

19.7

20

2CE04511046

2

10.1

12.1

24.7

25

2CE04511546

2

13.6

16.4

29.9

30

2CE04512046

2

19.5

23.5

38.8

40

DH048

(4.0)

208-3-60

13.1

110.0

2.3

5.2

10.0

None

--

--

33.9

45

2CE04510525

2

4.0

11.1

33.9

45

2CE04510725

2

5.6

15.5

38.4

45

2CE04511025

8.0

22.2

46.8

50

2CE04511525

11.9

33.0

60.3

70

2CE04512025

15.9

44.1

74.2

80

230-3-60

13.1

110.0

2.3

5.2

10.0

None

--

--

33.9

45

2CE04510525

2

5.3

12.7

34.9

45

2CE04510725

2

7.5

18.0

41.6

45

2CE04511025

10.6

25.5

50.9

60

2CE04511525

15.9

38.2

66.8

70

2CE04512025

21.2

51.0

82.7

90

460-3-60

6.7

54.0

1.3

2.6

5.0

None

--

--

17.3

20

2CE04510746

2

6.8

8.2

19.7

20

2CE04511046

2

10.1

12.1

24.7

25

2CE04511546

2

13.6

16.4

29.9

30

2CE04512046

2

19.5

23.5

38.8

40

575-3-60

5.1

44.0

1.3

2.0

4.0

None

--

--

13.4

15

2CE04511058

10.6

10.2

20.2

25

2CE04511558

15.9

15.3

26.6

30

2CE04512058

21.2

20.4

33.0

35

DH060

(5.0)

208-3-60

16.0

137.0

2.3

5.2

10.0

None

--

--

37.5

50

2CE04510525

2

4.0

11.1

37.5

50

2CE04510725

2

5.6

15.5

38.4

50

2CE04511025

8.0

22.2

46.8

50

2CE04511525

11.9

33.0

60.3

70

2CE04512025

15.9

44.1

74.2

80

2CE04513025

22.2

61.6

96.0

100

230-3-60

16.0

137.0

2.3

5.2

10.0

None

--

--

37.5

50

2CE04510525

2

5.3

12.7

37.5

50

2CE04510725

2

7.5

18.0

41.6

50

2CE04511025

10.6

25.5

50.9

60

2CE04511525

15.9

38.2

66.8

70

2CE04512025

21.2

51.0

82.7

90

2CE04513025

29.6

71.2

108.0

110

460-3-60

8.3

69.0

1.3

2.6

5.0

None

--

--

19.3

25

2CE04510746

2

6.8

8.2

19.7

25

2CE04511046

2

10.1

12.1

24.7

25

2CE04511546

2

13.6

16.4

29.9

30

2CE04512046

2

19.5

23.5

38.8

40

2CE04513046

2

28.8

34.6

52.8

60

575-3-60

6.4

58.0

1.3

2.0

4.0

None

--

--

15.0

20

2CE04511058

10.6

10.2

20.2

25

2CE04511558

15.9

15.3

26.6

30

2CE04512058

21.2

20.4

33.0

35

2CE04513058

30.4

29.3

44.1

45

1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block

accessories 2FB04700825 and 2FB04700846 are available for field installation.

Advertising
This manual is related to the following products: