March 2008 – York D*V User Manual

Page 10

Advertising
background image

DESCRIPTION:

PROJECT:

TAG:

DATE:

Gross Cooling Capacity [Btuh]:

150,000*

Design CFM:

4,800

Energy Efficiency Ratio:

10.65 EER**

Net Cooling Capacity [Btuh]:

144,000**

Net Cooling CFM:

4,800

Refrigerant:

R22

Charge:

12.13 Lbs./ circuit

Compressor No./Type:

2/Scroll

Refrigerant Circuits:

2 / Independent

Evaporator Coil Face Area:

13.03 [sq ft]

Rows/FPI :

3/10

Refrigerant Control:

TX Valve

Filters - Qty./Size:

2/14x20x2 & 4/14x25x2

Condenser Coil Face Area:

15.82 [sq ft]

Rows/FPI:

4/14

Evaporator Fan No./Type:

2/CENTRIFUGAL

Diameter x Width [in]:

12x9

Drive:

Adjustable Belt

Motor HP :

2.0 / 3.0

[Standard/Oversized]

Condenser Fan No./Type:

2/CENTRIFUGAL

Diameter x Width [in]:

15x15

Drive:

tl

e

B

e

l

b

a

t

s

u

j

d

A

Motor HP : 3.0

[Standard]

Operating Weight [lbs.]:

1335

Shipping Weight [lbs.]:

1395

Condensate Connection:

3 / 4 NPT

*Cooling performance is rated at 95

°

F ambient, 80

°

F entering dry bulb, 67

°

F wet bulb

and CFM listed. Gross capacity does not include the effect of fan motor heat.
**Rated in accordance with ARI Standard 360-2000

NOTE:

1. At high evaporator air flows, and wet bulb conditions, condensate carry-over may occur. Adjust airflow downward as necessary.

2. Values include pressure drop from wet coil and clean filters.

3. Shaded areas indicate oversize motors.

EVAPORATOR FAN PERFORMANCE

CONDENSER FAN PERFORMANCE

ELECTRICAL DATA – STANDARD MOTOR

ELECTRICAL DATA – OVERSIZED MOTOR

MODEL

SUPPLY

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

#

CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

4300

4800

DPV144

DPV144

DPV144

DPV144

DPV144

DPV144

DPV144

DPV144

717 1.06 792 1.23 862 1.41 928 1.58 989 1.75 1049 1.93 1100 2.10 1165 2.30 1210 2.50 1245 2.60
781 1.42 850 1.62 915 1.81 976 2.00 1035 2.20 1091 2.39 1144 2.58 1197 2.79 1245 2.96

-

-

5300

6600

848 1.87 912 2.08 972 2.29 1030 2.57 1085 2.72 1138 2.94 1189 3.15

-

-

-

-

-

-

EXTERNAL STATIC PRESSURE - Inches W.C.

EXTERNAL STATIC PRESSURE - Inches W.C.

MODEL OUTDOOR

0.2

0.4

0.6

0.8

1.0

1.2

#

CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

675 1.77 735 2.06 792 2.46 848 2.60 900 3.00

-

-

MODEL

VOLTAGE

COMPRESSOR

EVAPORATOR FAN

CONDENSER FAN

MIN. CCT.

MAX FUSE /

#

QTY

RLA

LRA

HP

FLA

HP

FLA

AMPACITY

CCT. BKR. AMP

208-230/3/60

2

@ 20.7 156.0

2.00

5.9

3.00

8.7

61.18

80

460/3/60

2

@ 10.0

75.0

2.00

2.8

3.00

4.0

29.30

35

575/3/60

2

@ 8.2

54.0

2.00

2.2

3.00

3.2

23.85

30

MODEL

VOLTAGE

COMPRESSOR

EVAPORATOR FAN

CONDENSER FAN

MIN. CCT.

MAX FUSE /

#

QTY

RLA

LRA

HP

FLA

HP

FLA

AMPACITY

CCT. BKR. AMP

208-230/3/60

2

@ 20.7 156.0

3.00

8.7

3.00

8.7

63.98

80

460/3/60

2

@ 10.0

75.0

3.00

4.0

3.00

4.0

30.50

40

575/3/60

2

@ 8.2

54.0

3.00

3.2

3.00

3.2

24.85

30

March 2008

DPV144 VERTICAL UNIT

AIR-COOLED SELF-CONTAINED

Form YK145.12-PA6 (308)

1 of 4

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

Page 10