SITE REQUIREMENTS

7

Location of hearth or Solid fuel

cooker

Solid, non combustible material

Thickness (W)

height (A)

Where the hearth abuts a wall and the solid

fuel cooker is not more than 50mm from the

wall

200mm

At least 300mm above the solid fuel

cooker and 1200mm above the

hearth(Use the largest value)

Where the hearth abuts a wall and the

appliance is more than 50mm but not more

than 300mm from the wall

75mm

At least 300mm above the solid fuel

cooker and 1200mm above the hearth

(Use the largest value)

Where the hearth does not abut a wall and

is no more than 150mm from the wallSee

note below

75mm

At least 300mm above the hearth

Note: there is no requirement for protection the wall where C is more than 150mm

WALLS ADJACENT TO HEARTHS