PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-

connecting line tubing.

2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical

Data Table.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaporator + adder for line set.

HC18A3X

2A + 0

–

–

–

–

–

–

HC30A3X

–

2A + 0

–

–

–

–

–

HC36B3X

–

2A + 5

2A + 0

–

–

–

–

HC42C3X

–

–

2A + 0

2A + 0

–

–

–

HC60C3X

–

–

–

2A + 5

2C + 2

2C + 0

–

HD24A3X

–

2A + 4

–

–

–

–

–

HD36B3X

–

–

2A + 0

–

–

–

–

HD48C3X

–

–

–

2A + 3

–

–

–

HD60D3X

–

–

–

2A + 5

2C + 2

2C + 0

–

MH24S59

–

2A + 6

2A + 0

–

–

–

–

MH30S65

–

2A + 6

2A + 0

–

–

–

–

AHP18B3X

2A + 0

–

–

–

–

–

–

AHP24B3X

2A + 0

2A + 0

–

–

–

–

–

AHP30B3X

–

2A + 5

2A + 0

–

–

–

–

AHP36C3X

–

–

2A + 0

2A + 0

–

–

–

AHP42C3X

–

–

–

2A + 0

–

–

–

AHP48D3X

–

–

–

–

2C + 2

2C + 0

–

AHP60D3X

–

–

–

2A + 5

2C + 2

2C + 0

–

AV24B2A

2A + 0

2A + 0

–

–

–

–

–

AV36C2A

–

–

2A + 0

2A + 0

–

–

–

AV48D2C

–

–

–

2A + 0

2C + 0

2C + 0

–

AV60D2C

–

–

–

–

2C + 0

2C + 0

–

F4FP024

0 –

–

–

–

–

–

F4FP030

–

0 –

–

–

–

–

F4FP040

–

–

0 –

–

–

–

F5FP045

–

–

–

2A + 5

2

–

–

F5FP048

–

–

–

2A + 3

0

–

–

F5FP060

–

–

–

2A + 5

2

0

–

F4FV060

–

–

–

2A + 0

0

0

–

FOOTNOTES:

1. For applications requiring a TXV use 1TVM series kit.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit

2FD06700224.

3. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

Additional R-22 Charge / Orifice Size for Various Matched Systems (Continued)

Outdoor Unit

THGD18

S21S1

THGD24

S21S1

THGD30

S21S1

THGD36

S21S1

THGD42

S21S1

THGD48

S21S1

THGD60

S21S1

Required Orifice or TXV

1

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2C1

1TVM2C1

1TVM2C1

Factory Charge, lbs-oz

7 - 3

7 - 7

8 - 12

9 - 1

11 - 14

13 - 4

15 - 5

Indoor Coil

2,3

Additional Charge, Oz