Unitary Products Group

NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH

TABLE 10: STEAM COIL CAPACITIES

1

, MBH @ 2 PSIG

2

UNIT

MODEL

STEAM COIL

MODEL

CFM

DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)

10

30

50

70

LA300

1NF0454

6,000

471

424

380

330

8,000

535

483

432

380

10,000

592

535

478

422

12,000

642

580

518

456

LB360

8,000

535

483

432

380

10,000

592

535

478

422

12,000

642

580

518

456

14,000

687

621

555

489

1.

These capacities do not include any blower motor heat.

2.

Multiply these capacities by the factors in Table 11 to correct for higher steam pressure.

TABLE 11: CORRECTION FACTORS FOR HIGH STEAM

STEAM PRESSURE (PSIG)

5

10

15

20

25

CAPACITY CORRECTION FACTOR

1.05

1.12

1.19

1.25

1.30