STEAM COILS (LA300 & LB360 only): A steam coil is avail-
able on the 25 & 30 Ton for installation between the blower
and coil modules of both horizontal and vertical units. Since
the casing matches the dimensions and the finish of the basic
unit, it becomes an integral part of the unit after installation.
The coil slides out of the casings for easy installation and is
pitched in the casings to facilitate condensate drainage. The
coil has copper tubes that have been mechanically expanded
into aluminum fins. Both headers are located on the same
end of the coil. The coil is leak-tested at 325 psig and dried
before the connections are capped for storage and shipping.

BLOWER MOTORS: Different HP motors are available for
each unit to meet almost any air delivery requirement. All
motors are UL approved, have permanently lubricated ball
bearings and are field-mounted within the insulated cabinet of
the units to minimize the transmission of sound to the sur-

rounding space. 5 HP motors are inherently protected. 7.5
HP - 15 HP require motor overload protection.

DRIVE PACKAGES:

Different size pulleys and belts are

available for each unit to provide a blower RPM range to
meet almost any air delivery requirement. Variable pitch
motor pulleys can be adjusted to provide the proper blower
RPM. All drive packages are rated at least 25% above the
nominal HP rating of the blower motor. Two-groove pulleys
and two belts are provided on every drive package rated at 5
HP and above.

STARTERS AND HEATER ELEMENTS (7.5 - 15 HP): The
blower motors that are available for the units do not have
inherent protection and require external motor overload pro-
tection. See details in Table 7.

TABLE 1: STATIC RESISTANCES FOR UNIT ACCESSORIES

UNIT MODEL

ACCESSORY

CFM

LA300

8,000

9,000

10,000

11,000

12,000

Hot Water Coil

0.06

0.07

0.08

0.09

0.10

Steam Coil

0.11

0.14

0.17

0.20

0.23

LB360

10,000

11,000

12,000

13,000

14,000

Hot Water Coil

0.08

0.09

0.10

0.12

0.14

Steam Coil

0.17

0.20

0.23

0.27

0.31

LB480

12,800

14,400

16,000

17,600

19,200

Hot Water Coil

0.11

0.13

0.15

0.17

0.20

LB600

16,000

18,000

20,000

22,000

24,000

Hot Water Coil

0.15

0.18

0.21

0.24

0.28

TABLE 2: UNIT MOUNTING DIMENSIONS

1

LA/LB

UNIT

DIMENSIONS, INCHES

AX

BX

CX

300

69-1/4

49-1/16

26-5/8

360

69-1/4

49-1/16

26-5/8

480

84

50-9/16

34

1.

See Figure 4 for dimensions AX, BX and CX.