York LB360 User Manual

Page 20

Advertising
background image

036-21335-002-A-1102

20

Unitary Products Group

TABLE 21: FAN PERFORMANCE DATA - 40 TON

1

RPM

CFM

12,800

14,400

16,000

17,600

19,200

SP

2

BHP

K

W

SP

2

BHP

K

W

SP

2

BHP

K

W

SP

2

BHP

K

W

SP

2

BHP

K

W

600

0.20

4.3

3.7

-

-

-

-

-

-

-

-

-

-

-

-

640

0.38

4.8

4.1

0.19

5.6

4.8

-

-

-

-

-

-

-

-

-

700

0.65

5.5

4.7

0.47

6.4

5.5

0.28

7.2

6.2

-

-

-

-

-

-

775

0.99

6.5

5.6

0.84

7.4

6.4

0.66

8.4

7.2

0.46

9.4

8.1

0.23

10.4

9.0

800

1.11

6.8

5.9

0.96

7.8

6.7

0.79

8.8

7.6

0.59

9.8

8.4

0.36

10.8

9.3

900

1.65

8.1

7.0

1.52

9.3

8.0

1.36

10.5

9.0

-

-

-

-

-

-

915

1.73

8.3

7.2

1.60

9.5

8.2

1.44

10.7

9.2

-

-

-

-

-

-

1.

Unit resistance is based on a dry evaporator coil and clean filters.

2.

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.

TABLE 22: FAN PERFORMANCE DATA - 50 TON

1

RPM

CFM

16,000

18,000

20,000

22,000

24,000

SP

2

BHP

K

W

SP

2

BHP

K

W

SP

2

BHP

K

W

SP

2

BHP

K

W

SP

2

BHP

K

W

600

0.82

6.0

5.2

0.59

7.2

6.2

0.35

8.4

7.2

0.08

9.7

8.4

-

-

-

660

1.17

7.3

6.3

0.96

8.5

7.3

0.73

9.8

8.5

0.45

11.2

9.7

0.14

12.7

11.0

700

1.40

8.2

7.1

1.21

9.4

8.1

0.98

10.7

9.2

0.70

12.2

10.5

0.40

13.7

11.8

760

1.76

9.5

8.2

1.59

10.8

9.3

1.38

12.3

10.6

1.11

13.8

11.9

0.81

15.6

13.5

800

2.00

10.4

9.0

1.85

11.8

10.2

1.64

13.3

11.5

1.38

14.9

12.9

1.09

16.9

14.6

900

2.60

12.8

11.0

2.49

14.5

12.5

2.35

16.0

13.8

-

-

-

-

-

-

930

2.78

13.5

11.6

2.68

15.3

13.2

-

-

-

-

-

-

-

-

-

1.

Unit resistance is based on a dry evaporator coil and clean filters.

2.

Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.