LOCATION

Use the following guidelines to select a suitable location for
these units:

1.

Unit is designed for outdoor installation only.

2.

Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit
on either north or east side of building.

3.

Suitable for mounting on roof curb.

4.

For ground level installation, use a level concrete slab
with a minimum thickness of 4 inches. The length and
width should be at least 6 inches greater than the unit
base rails. Do not tie slab to the building foundation.

5.

Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed on
a solid, level roof curb or appropriate angle iron frame.

6.

Maintain level tolerance to 1/2” across the entire width
and length of unit.

FIGURE 5 -

PREDATOR MagnaDRY™ DR150 COMPONENT LOCATION

Simplicity™ Control

board w/screw

connectors for T-stat

wiring and Network

Connection

Disconnect

location (optional

disconnect switch)

Filter access

(2" throw-away)

Filter drier (solid core)

Condenser Section

Belt-drive blower

motor

Slide out motor

and blower

assembly for easy

adjustment and

service

Power ventor

motor

20-gauge

aluminized steel

tubular heat

exchanger for

long life

(stainless steel

option)

Two-stage gas heating to

maintain warm,

comfortable temperature

Intelligent control

board for safe and
efficient operation

Slide-out drain pan

with brass ¾" NPT,

female connection

Compressor #1 access

(high-efficiency

compressor w/crankcase

heater)

Side entry power

and control wiring

knockouts

Tool-less door

latch

Roof curbs in eight-and

fourteen-inch heights.

Roof curbs for

transitioning from York

Sunline TM footprint to

the DM/DH/DJ Series

footprint are available

(field-installed accessory)

Base rails w/

forklift slots

( three sides)

and lifting

holes

Compressor #2

access

(high-efficiency

compressor w/

crankcase heater)

Dual stage cooling

for maximum

comfort

Second model

nameplate inside

hinged access panel

TABLE 1:

UNIT VOLTAGE LIMITATIONS

Power Rating

*

*.

Utilization range “A” in accordance with ARI Standard 110.

Minimum

Maximum

208/230-3-60

187

252

460-3-60

432

504

575-3-60

540

630

TABLE 2:

UNIT TEMPERATURE LIMITATIONS

Temperature

Min.

Max.

Wet Bulb Temperature (

°F) of Air on

Evaporator Coil

57

72

Dry Bulb Temperature (

°F) of Air on

Condenser Coil

0

*

*.

A low ambient accessory is available for operation
down to -20°F.

125