York PREDATOR DR120 User Manual
Page 63
127878-YIM-B-0606
Unitary Products Group
63
TABLE 42: IGNITION CONTROL FLASH CODES
FLASHES
FAULT CONDITIONS
CHECK
STEADY ON
Control Failure
Control
HEARTBEAT
Normal Operation
1
Not Applicable
2
Pressure Switch
Stuck Closed
Pressure Switch
3
Pressure Switch Failed
To Close
Venter Pressure Switch
Vent Blocked
4
Limit Switch Open
Main Limit
AUX Limit
5
Flame Present With Gas
Off First Stage Gas Valve
Energized With W1 Off
Second Stage Gas Valve
Energized With First
Stage
Gas Valve Off
Gas Valve
6
Ignition Lockout
Gas Flow
Gas Pressure
Gas Valve
Flame Sensor
STEADY OFF
No Power Or Control
Failure
24VAC or Control
TABLE 43: REHEAT CONTROL BOARD FLASH
CODES
FLASH CODES
DESCRIPTION
On Steady
This is a Control Failure
1 Flash
Not Applicable
2 Flashes
Hot Gas Reheat is on with Y1 Output
(No Call for Cooling)
3 Flashes
Y1, Y2, and Hot Gas Reheat is on because of
a call for Y1 and Humidistat. See alt operation
OFF
No Power or Control Failure