York PREDATOR DR120 User Manual

Page 63

Advertising
background image

127878-YIM-B-0606

Unitary Products Group

63

TABLE 42: IGNITION CONTROL FLASH CODES

FLASHES

FAULT CONDITIONS

CHECK

STEADY ON

Control Failure

Control

HEARTBEAT

Normal Operation

1

Not Applicable

2

Pressure Switch
Stuck Closed

Pressure Switch

3

Pressure Switch Failed
To Close

Venter Pressure Switch
Vent Blocked

4

Limit Switch Open

Main Limit
AUX Limit

5

Flame Present With Gas
Off First Stage Gas Valve
Energized With W1 Off
Second Stage Gas Valve
Energized With First
Stage
Gas Valve Off

Gas Valve

6

Ignition Lockout

Gas Flow
Gas Pressure
Gas Valve
Flame Sensor

STEADY OFF

No Power Or Control
Failure

24VAC or Control

TABLE 43: REHEAT CONTROL BOARD FLASH

CODES

FLASH CODES

DESCRIPTION

On Steady

This is a Control Failure

1 Flash

Not Applicable

2 Flashes

Hot Gas Reheat is on with Y1 Output
(No Call for Cooling)

3 Flashes

Y1, Y2, and Hot Gas Reheat is on because of
a call for Y1 and Humidistat. See alt operation

OFF

No Power or Control Failure