TABLE 22: COOLING CAPACITIES FOR DJ300 AT 115°F

RETURN AIR

OUTDOOR AMBIENT TEMPERATURE (°F): 115

CFM

WB

TEMP °F

GROSS

CAPACITY

1

(MBH)

INPUT

POWER

2

(kW)

GROSS SENSIBLE CAPACITY

1

(MBH)

(RETURN AIR DRY BULB TEMP. - (°F) )

86

83

80

77

74

71

68

7500

72

279.1

30.03

177.6

156.2

134.8

113.4

92.0

#N/A

#N/A

67

272.6

29.81

231.6

210.3

188.9

167.5

146.1

124.7

103.3

62

266.0

28.91

266.0

245.2

223.8

202.4

181.0

159.6

138.3

57

250.9

28.79

250.9

243.6

222.2

200.8

179.4

158.1

136.7

8750

72

286.9

30.20

195.1

169.8

144.6

119.3

94.0

#N/A

#N/A

67

280.1

29.98

253.1

227.9

202.6

177.3

152.0

126.8

101.5

62

273.3

29.07

273.3

262.9

240.0

214.8

189.5

164.2

138.9

57

257.9

28.96

257.9

254.2

238.3

213.1

187.8

162.5

137.3

10000

72

294.6

30.38

212.7

183.5

154.4

125.2

96.0

#N/A

#N/A

67

287.6

30.16

274.6

245.5

216.3

187.1

158.0

128.8

99.7

62

280.7

29.24

280.7

280.7

256.3

227.1

198.0

168.8

139.6

57

264.8

29.13

264.8

264.8

254.5

225.3

196.2

167.0

137.8

11250

72

301.4

30.66

227.3

194.1

160.9

127.7

94.5

#N/A

#N/A

67

294.3

30.44

287.8

258.7

225.5

192.3

159.1

125.9

92.7

62

287.2

29.52

287.2

287.2

267.2

234.0

200.8

167.6

134.3

57

270.9

29.40

270.9

270.9

265.3

232.1

198.9

165.7

132.5

12500

72

308.2

30.95

242.0

204.8

167.5

130.2

93.0

#N/A

#N/A

67

300.9

30.72

300.9

272.0

234.7

197.4

160.2

122.9

85.7

62

293.6

29.79

293.6

293.6

278.1

240.8

203.6

166.3

129.0

57

277.0

29.68

277.0

277.0

276.1

238.9

201.6

164.3

127.1

1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-

priate blower performance table for the kW of the supply air blower motor.

2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.