NOTE:

A 1” clearance must be provided between any com-

bustible material and the supply air ductwork for a distance of
3 feet from the unit.

NOTE:

The products of combustion must not be allowed to

accumulate within a confined space and recirculate.

NOTE:

Locate unit so that the vent air outlet hood is at least:

Three (3) feet above any force air inlet located within 10
horizontal feet (excluding those integral to the unit).

Four (4) feet below, 4 horizontal feet from, or 1 foot
above any door or gravity air inlet into the building.

Four (4) feet from electric and gas meters, regulators
and relief equipment.

NOTE:

All entry holes should be field sealed to prevent rain

water entry into building.

FIGURE 3: UNIT DIMENSIONS DJ180, 210, 240 & 300 (FRONT VIEW)

11-1/2

(A) CONTROL WIRING
ENTRY

COIL
GUARD
KIT

CONDENSER
COILS

All dimensions are in inches. They are
subject to change without notice.
Certified dimensions will be provided
upon request.

(B) POWER
WIRING ENTRY

5

9-3/4

21.00

6-3/8

7-1/8

35

5-7/8

136-1/4

GAS OR
ELECTRIC
HEAT ACCESS

DOT PLUG
(For pressure
drop reading)

BLOWER
COMPARTMENT
ACCESS
(Auxillary)

(C) GAS
SUPPLY
ENTRY

CONTROL BOX
ACCESS

VENT AIR
OUTLET
HOODS

BLOWER MOTOR
ACCESS

BLOWER
ACCESS

52-5/8

180-19/32

COMPRESSOR ACCESS
(See detail X)

DISCONNECT
SWITCH
LOCATION

ECONOMIZER / MOTORIZED DAMPER
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail Y)

92

46-5/8

35-1/4

33

2-3/4

3-3/4

(B) POWER WIRING
ENTRY

BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)

(A) CONTROL WIRING
ENTRY

21-1/2

11-1/8

(D)
GAS SUPPLY
ENTRY

UNIT BASE RAILS

Shown separately to illustrate
Bottom Duct openings. Power
and Gas Piping Connection
location.

RETURN

AIR

NOTE:

For curb mounted units, refer to the curb hanger
dimensions of the curb for proper size of the
supply and return air duct connections.

12-1/2

9-1/4

8-1/8

46-5/8

9-3/4

COMBUSTION
AIR INLET HOOD

SUPPLY

AIR

TABLE 38: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

36”

Back

24” (Less Economizer)

49” (With Economizer)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

36”

Below Unit

1

1. Units may be installed on combustible floors made from wood

or class A, B, or C roof covering material.

0”

Above Unit

2

2. Units must be installed outdoors. Overhanging structures or

shrubs should not obstruct condenser air discharge outlet.

72” With 36” Maximum

Horizontal Overhang (For

Condenser Air Discharge)

TABLE 39: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

A

1-1/8” KO

Control Wiring

Front

3/4” NPS (Fem.)

Bottom

B

3-5/8” KO

Power Wiring

Front

3” NPS (Fem.)

Bottom

C

2-3/8” KO

Gas Piping (Front)

1

1. One-inch Gas Piping MPT Required.

D

1-11/16” Hole

Gas Piping (Bottom)

1,2

2. Opening in the bottom to the unit can be located by the side in

the insulation.

Advertising
This manual is related to the following products: