Xantrex Technology ENERGY HW 1000 User Manual

Page 58

Advertising
background image

5–6

975-0467-01-01

E07

Over-temperature
warning

Inverting

•

Reduce the loads connected to the AC
outlet of the unit.

•

Check that the ventilation grille is not
blocked.

•

Check for ambient temperature and move
the unit to a cooler location whenever
possible.

E08

not used

E09

not used

E10

High battery voltage
(> 15.5 V)

AC shore
power

•

Check for external charging sources, such
as an over voltage alternator, and
disconnect if necessary.

•

Confirm that the external charging source is
not the cause. The error may be caused by
the internal battery charger system. Call
Xantrex for support.

E11

Over-temperature
detected on the AC
transfer relay

AC shore
power

•

Reduce the loads connected to the AC
outlet of the unit.

•

Check that the ventilation grille is not
blocked.

•

Check for ambient temperature and move
the unit to a cooler location whenever
possible.

E12

Battery is bad or
external DC load is
connected to the
battery.

AC shore
power

•

Check the battery bank.
NOTE: The battery voltage did not rise
above 5 Vdc after 1 minute or 10 Vdc after
15 minutes.

•

Check that the external DC load current
consumption is below the charging current
setting.

•

Disconnect the DC load or increase the
charger current setting.

Table 5-1 Error Codes Displayed on the Display Panel Screen

Error Code Condition

Mode

Action