York STELLAR PLUS H4DH018 THRU 060 User Manual

Page 4

Advertising
background image

036-21020-003 Rev. C (0203)

4

Unitary Products Group

- = Not applicable

COOLING CAPACITY - With Air Handler Coils

UNIT MODEL

AIR HANDLER

COIL

1

MODEL

1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.

COOLING

MODEL

ELECTRIC

2

HEAT KW

2. Single phase units require single phase 2HK heaters.

W

RATED

CFM

NET MBH

SEER

W/O TXV

SEER

+ TXV

3

3. TXV = Use 1TV700 Series Kit.

EER

TOTAL SENS.

1 PH 12 SEER AC / N1AH + G2FD

H4DH018S06

N1AHB0806

2,5,8,10

17

G2FD024(S,H)17

650

18.6

14.0

12.50

-

10.80

N1AHB0806

2,5,8,10

17

G2FD030(S,H)17

650

19.0

14.3

12.50

-

10.80

H4DH024S06

N1AHB0806

2,5,8,10

17

G2FD024(S,H)17

850

23.4

17.6

12.10

-

10.90

N1AHB0806

2,5,8,10

17

G2FD030(S,H)17

850

23.4

17.6

12.00

-

10.90

H4DH030S06

N1AHB1206

5,8,10,15,19

17

G2FD030(S,H)17

1030

29.4

22.1

-

12.40

10.50

N1AHB1206

5,8,10,15,19

17

G2FD036(S,H)17

1030

30.0

22.5

12.40

-

10.60

H4DH036S06

N1AHB1206

5,8,10,15,19

17

G2FD036(S,H)17

1200

35.8

26.5

12.15

-

11.20

N1AHB1206

5,8,10,15,19

17

G2FD046(S,H)17

1200

36.2

26.8

12.30

-

11.20

N1AHD1406

5,8,10,15,19

24

G2FD048(S,H)24

1200

38.0

28.1

13.50

-

12.05

N1AHD1406

5,8,10,15,19

24

G2FD060(S,H)24

1200

38.5

28.5

13.70

-

12.20

H4DH042S06

N1AHC1606

5,8,10,15,20

21

G2FD042(S,H)21

1400

40.5

30.4

12.00

-

10.60

N1AHC1606

5,8,10,15,20

21

G2FD048(S,H)21

1400

42.0

31.5

12.35

-

10.90

H4DH048S06

N1AHC1606

5,8,10,15,20

21

G2FD048(S,H)21

1600

48.5

36.4

12.35

-

11.15

N1AHD2006

8,10,15,20,25,30

24

G2FD060(S,H)24

1600

50.0

37.5

12.50

13.00

11.45

H4DH060S06

N1AHD2006

8,10,15,20,25,30

24

G2FD060(S,H)24

1800

58.5

43.9

12.00

12.50

11.05

N1AHD2006

8,10,15,20,25,30

24

G2FD061H24

2000

60.0

45.0

12.50

12.50

11.25

1 PH 12 SEER AC / N1VS - VARIABLE SPEED

H4DH018S06

N1VSB12

10,15,18

17

G2FD024(S,H)17

650

20.0

15.0

-

13.50

11.20

H4DH024S06

N1VSB12

10,15,18

17

G2FD024(S,H)17

850

24.4

18.3

13.50

-

12.10

N1VSB12

10,15,18

17

G2FD036(S,H)17

860

24.6

18.5

13.55

-

12.10

H4DH030S06

N1VSB12

10,15,18

17

G2FD036(S,H)17

1030

31.0

23.3

13.40

-

11.30

N1VSB12

10,15,18

17

G2FD046(S,H)17

1000

32.6

22.8

13.50

-

11.50

H4DH036S06

N1VSB12

10,15,18

17

G2FD036(S,H)17

1200

35.6

26.7

13.10

-

12.05

N1VSC16

10,15,18

21

G2FD048(S,H)21

1200

38.0

28.5

14.10

-

12.55

H4DH042S06

N1VSC16

10,15,18

21

G2FD048(S,H)21

1380

42.5

31.9

13.35

-

11.70

H4DH048S06

N1VSC16

10,15,18

21

G2FD048(S,H)21

1590

49.0

36.8

13.00

-

11.70

N1VSD20

10,15,18,30

24

G2FD060(S,H)24

1600

50.5

37.9

13.10

-

11.90

H4DH060S06

N1VSD20

10,15,18,30

24

G2FD060(S,H)24

1780

59.0

44.3

12.40

-

11.40

N1VSD20

10,15,18,30

24

G2FD061H24

1780

60.5

45.4

-

13.00

11.80

1 PH 12 SEER AC / F2RP / RC / FP / FC / FV

4,5

4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC

.

models. All ratings remain the same.

5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.

H4DH018S06

F2RC/FC024

5,8,10

18

-

650

18.6

14.0

12.20

-

10.90

F2RP/FP018

2,5,8

18

-

650

18.0

13.5

12.00

-

10.70

F2RP/FP024

5,8,10

18

-

650

18.6

14.0

12.50

-

11.00

H4DH024S06

F2RC/FC024

5,8,10

18

-

850

23.0

17.3

12.00

-

10.80

F2RC/FC030

5,8,10,15

18

-

850

23.4

17.6

12.00

-

10.90

F2RP/FP024

5,8,10

18

-

850

24.0

18.0

12.10

-

10.90

F2RP/FP030

5,8,10,15

18

-

850

24.4

18.3

12.00

-

10.80

F2FP040

5,8,10,15

21

-

850

24.8

18.6

-

12.70

11.30

H4DH030S06

F2RC/FC030

5,8,10,15

18

-

1030

28.4

21.3

12.00

-

10.50

F2RP/FP030

5,8,10,15

18

-

1030

30.0

22.5

12.30

12.50

10.50

F2RP/FP036

5,8,10,15,19

21

-

1030

31.0

23.3

12.50

-

10.60

F2FP048

5,8,10,15,20,25

24

-

1030

31.4

23.6

12.60

-

10.70

H4DH036S06

F2RC/FC036

5,8,10,15

21

-

1200

35.6

26.7

12.35

-

11.10

F2RP/FP036

5,8,10,15,19

21

-

1200

36.2

27.2

12.50

-

11.45

F2RP/FP042

5,8,10,15

21

-

1200

36.4

27.3

12.50

-

11.50

F2FP045

5,8,10,15

24

-

1200

38.0

28.5

-

13.50

12.20

F2FP048

5,8,10,15,20,25

24

-

1200

36.8

27.6

12.80

-

11.80

H4DH042S06

F2RP/FP042

5,8,10,15

21

-

1400

40.5

30.4

12.00

-

10.50

F2FP045

5,8,10,15

24

-

1400

42.5

31.9

13.00

-

11.20

F2FP048

5,8,10,15,20,25

24

-

1400

41.5

31.1

12.20

-

10.65

H4DH048S06

F2FP048

5,8,10,15,20,25

24

-

1600

48.0

36.0

12.00

-

11.00

F2FP060

5,8,10,15,20,25

24

-

1600

49.0

36.8

12.30

-

10.95

F2FV060

8,10,15,20,25

24

-

1600

50.5

37.9

13.10

-

11.90

H4DH060S06

F2FP060

5,8,10,15,20,25

24

-

1900

59.0

44.3

12.00

-

10.90

F2FV060

8,10,15,20,25

24

-

1780

59.0

44.3

-

12.40

11.40

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8

0°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in
watt-hours during the same period.

Advertising