Rear panel j1 connector, Figure 1.5 programming and monitoring j1 connector, Figure 1.5 – Xantrex Technology XPR 150-40 User Manual
Page 24: Programming and monitoring j1 connector
![background image](/manuals/230180/24/background.png)
About The XPR Power Supply
Rear Panel Connectors and Switch
22
Operating Manual for XPR Series Power Supply
Rear Panel J1
Connector
The J1 Programming and Monitoring connector is a 15-terminal wire clamp
connector located on the power supply’s rear panel. See
. The J1 connector
provides access to the following functions:
•
Remote programming of output voltage AND/OR current limit
•
Remote monitoring of calibrated readback signals for output voltage and output
current
•
Remote control of the shutdown function using TTL-compatible signals
(Interlock module)
•
15 V user supply to allow for contract closure control of the remote on/off line,
current limited
Figure 1.5 Programming and Monitoring J1 Connector
for the list of the J1 connector terminal numbers, their
references, and corresponding functions.
1 Output Voltage Programming Input
2 Output Current Limit Programming Input
3 Program Return
4 Output Voltage Monitor
5 Output Current Monitor
6 Monitor Return
7 N/C
8 Ground Return
9 + 15 V User Signal
10 N/C
11 Interlock Return (–)
12 Interlock Signal (+)
13 N/C
14 Shutdown Return (–)
15 Shutdown (+)