Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

Continued on Page 22.

COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO.

CZH04811

INDOOR COIL MODEL NO.

FC62D + MV20D

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

950

1000

1050

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

35.4 36.6 36.2 39.8 42.3 36.1 37.2 36.8 40.2 42.9 36.8 37.8 37.4 40.6 43.4

S.C.

34.3 31.8 26.9 27.2 21.7 34.8 32.5 27.6 27.8 22.0 35.3 33.3 28.2 28.5 22.3

K.W.

1.50 1.50 1.49 1.48 1.48 1.50 1.49 1.49 1.48 1.47 1.49 1.49 1.49 1.47 1.47

75

T.C.

34.0 34.9 34.5 37.8 40.4 34.6 35.4 35.0 38.2 40.9 35.2 36.0 35.5 38.6 41.5

S.C.

32.9 31.0 26.2 26.4 21.0 33.4 31.7 26.8 27.0 21.3 33.9 32.4 27.4 27.6 21.7

K.W.

1.81 1.81 1.81 1.80 1.79 1.81 1.81 1.80 1.79 1.78 1.80 1.80 1.80 1.79 1.78

85

T.C.

32.5 33.1 32.8 35.7 38.5 33.1 33.7 33.2 36.2 39.0 33.7 34.2 33.6 36.6 39.5

S.C.

31.5 30.2 25.5 25.5 20.3 32.0 30.9 26.0 26.1 20.7 32.5 31.6 26.6 26.7 21.1

K.W.

2.12 2.12 2.12 2.11 2.10 2.12 2.12 2.12 2.11 2.10 2.12 2.12 2.11 2.11 2.09

95

T.C.

31.1 31.4 31.1 33.7 36.6 31.7 31.9 31.4 34.2 37.1 32.2 32.4 31.7 34.6 37.6

S.C.

30.1 29.4 24.8 24.7 19.6 30.6 30.1 25.3 25.3 20.0 31.1 30.8 25.8 25.8 20.4

K.W.

2.44 2.44 2.44 2.43 2.41 2.43 2.43 2.43 2.43 2.41 2.43 2.43 2.43 2.42 2.40

105

T.C.

29.4 29.7 28.9 31.5 34.2 30.0 30.2 29.3 31.9 34.6 30.5 30.7 29.6 32.3 35.0

S.C.

28.5 27.8 23.8 23.8 18.7 28.9 28.5 24.3 24.4 19.1 29.4 29.1 24.8 24.9 19.6

K.W.

2.86 2.87 2.87 2.87 2.84 2.86 2.86 2.86 2.86 2.84 2.86 2.86 2.86 2.85 2.84

115

T.C.

27.8 28.0 26.9 29.3 31.9 28.4 28.6 27.2 29.7 32.2 28.9 29.1 27.6 30.1 32.5

S.C.

26.9 26.3 22.9 23.0 17.8 27.4 26.9 23.4 23.5 18.3 27.8 27.5 23.9 24.1 18.7

K.W.

3.28 3.28 3.29 3.29 3.26 3.27 3.28 3.28 3.27 3.26 3.27 3.27 3.28 3.27 3.26

125

T.C.

26.2 26.4 24.8 27.1 29.6 26.7 26.9 25.2 27.5 29.8 27.2 27.5 25.6 27.9 30.0

S.C.

25.4 24.8 21.9 22.1 16.9 25.8 25.4 22.4 22.7 17.4 26.2 26.0 22.9 23.3 17.9

K.W.

3.69 3.70 3.71 3.71 3.67 3.69 3.69 3.70 3.69 3.67 3.69 3.69 3.70 3.68 3.68

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

AV/SV48D

0.97 0.97 1.00

AV/SV60D

0.97 0.97 1.00

F4FV060

0.99 0.98 1.01

MV16C

FC/MC/PC48C

1.00 1.00 0.99

MV16C

FC/MC/PC48D

1.00 1.00 0.99

MV16C

UC48D

1.00 1.00 0.99

MV20D

FC/MC/PC48D

1.00 1.00 1.00

MV20D

UC48D

1.00 1.00 1.00

MV20D

FC/MC62D

1.00 1.00 1.00

Advertising