Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO.

CZH06011

INDOOR COIL MODEL NO.

FC62D + MV20D

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

1100

1150

1200

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

38.1 44.0 43.9 47.7 52.4 39.7 44.2 44.3 48.1 53.0 41.4 44.3 44.7 48.5 53.5

S.C.

37.2 35.7 30.6 30.0 24.5 38.8 36.5 31.2 30.6 24.9 40.4 37.3 31.7 31.2 25.3

K.W.

3.20 1.94 1.94 1.91 1.92 2.79 1.94 1.94 1.91 1.90 2.37 1.95 1.94 1.92 1.88

75

T.C.

37.5 42.0 42.0 45.7 50.2 39.2 42.4 42.3 46.1 50.8 40.8 42.8 42.7 46.5 51.3

S.C.

36.6 35.0 29.8 29.4 23.8 38.2 35.8 30.4 30.0 24.2 39.8 36.6 30.9 30.6 24.6

K.W.

3.20 2.36 2.36 2.33 2.34 2.78 2.36 2.36 2.34 2.32 2.37 2.37 2.36 2.35 2.31

85

T.C.

37.0 40.1 40.0 43.8 48.1 38.6 40.7 40.4 44.2 48.6 40.2 41.3 40.7 44.5 49.1

S.C.

36.1 34.2 29.0 28.7 23.1 37.7 35.0 29.6 29.3 23.5 39.2 35.8 30.1 29.9 23.8

K.W.

3.20 2.78 2.78 2.75 2.76 2.78 2.78 2.78 2.76 2.75 2.37 2.78 2.78 2.77 2.74

95

T.C.

36.5 38.2 38.1 41.9 45.9 38.1 39.0 38.4 42.2 46.4 39.7 39.8 38.7 42.5 46.9

S.C.

35.6 33.5 28.2 28.1 22.4 37.1 34.3 28.8 28.7 22.7 38.7 35.0 29.3 29.2 23.1

K.W.

3.20 3.19 3.20 3.17 3.17 2.78 3.20 3.20 3.18 3.17 2.37 3.20 3.20 3.19 3.17

105

T.C.

34.2 35.5 35.3 38.8 42.7 35.4 36.1 35.6 39.1 43.1 36.6 36.7 35.8 39.3 43.5

S.C.

33.4 31.9 26.7 26.8 21.0 34.6 32.6 27.3 27.3 21.4 35.7 33.2 27.8 27.8 21.8

K.W.

3.76 3.75 3.75 3.73 3.73 3.48 3.75 3.75 3.74 3.73 3.20 3.76 3.76 3.75 3.74

115

T.C.

32.0 32.9 32.6 35.8 39.7 32.8 33.3 32.9 36.0 39.9 33.5 33.7 33.1 36.3 40.2

S.C.

31.3 30.4 25.3 25.4 19.7 32.0 30.9 25.9 25.9 20.1 32.8 31.5 26.4 26.4 20.5

K.W.

4.30 4.29 4.29 4.28 4.28 4.16 4.29 4.29 4.28 4.28 4.02 4.29 4.29 4.29 4.28

125

T.C.

29.9 30.3 30.0 32.7 36.6 30.2 30.5 30.1 33.0 36.7 30.5 30.6 30.3 33.2 36.9

S.C.

29.2 28.9 23.9 24.1 18.3 29.5 29.3 24.4 24.5 18.8 29.8 29.7 24.9 24.9 19.3

K.W.

4.84 4.82 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

AV/SV60D

0.99 0.99 1.00

F4FV060

0.99 0.99 1.02

MV20D

FC/MC/PC60D

0.95 0.95 1.00

MV20D

UC60D

0.95 0.95 1.00

MV20D

FC/MC62D

1.00 1.00 1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*C20

FC/PC60C

0.97 0.97 1.01

PV8*C20

FC/MC/PC60D

0.97 0.97 1.01

PV8*C20

UC60D

0.97 0.97 1.01

P(C,V)9*C20

FC/PC60C

0.96 0.96 1.01

P(C,V)9*C20

FC/MC/PC60D

0.96 0.96 1.01

P(C,V)9*C20

UC60D

0.96 0.96 1.01

P(C,V)9*D20

FC/MC/PC60D

0.95 0.95 1.00

P(C,V)9*D20

UC60D

0.95 0.95 1.00

PV8*C20

FC/MC62D

1.02 1.02 1.01

P(C,V)9*C20

FC/MC62D

1.01 1.01 1.00

P(C,V)9*D20

FC/MC62D

1.00 1.00 1.00

P(C,V)9*D20

HC60D 0.95

0.95

1.00

Y*9C*D20 FC/MC62D

0.98

0.97

1.03

Y*(8,L)C*C20 FC/PC60C

0.97

0.95

1.01

Y*9C*C20 FC/PC60C

0.97

0.95

1.02

Y*9C*D20 HC60

0.95

0.94

1.02

Y*(8,L)C*C20 HD60

0.98

0.95

1.01

Y*9C*C20 HD60

0.98

0.97

1.03

Y*9C*D20 HD60

0.99

0.97

1.03

Y*(8,L)C*C20 UC60C

0.94

0.91

1.01

Y*9C*C20 UC60C

0.93

0.90

1.02

Y*9C*D20 UC60D

0.94

0.92

1.02

G*9V*D20 FC/MC62D

0.98

0.97

1.03

G*9V*C20 FC/PC60C

0.97

0.95

1.02

G*9V*D20 HC60

0.95

0.94

1.02

G*9V*C20 HD60

0.98

0.97

1.03

G*9V*D20 HD60

0.99

0.97

1.03

G*9V*C20 UC60C

0.93

0.90

1.02

G*9V*D20 UC60D

0.94

0.92

1.02

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

Advertising