Sound Performance

Electric Heat Multipliers

Voltage

kW Capacity Multipliers

1

1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for

heaters applied at lower voltages.

Nominal

Applied

240

208

0.75

230

0.92

480

460

0.92

600

575

0.92

ZJ/ZR/ZF Indoor Sound Power Levels

Size

(Tons)

CFM

ESP

(IWG)

Blower

Sound Power, dB (10

-12

) Watts

Sound Rating

1

dB (A)

Octave Band Centerline Frequency (Hz)

RPM

BHP

63

125

250

500

1000

2000

4000

8000

180 (15)

6000

1.0

1,080

4.6

91

88

90

90

87

85

81

81

76

210 (17.5)

7000

1.0

940

5.1

85

84

84

82

81

81

77

74

69

240 (20)

8000

1.0

1,020

6.6

86

85

85

83

82

82

78

75

70

300 (25)

10000

1.3

1,160

12.5

92

91

91

89

88

88

84

81

76

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values

provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.

ZJ/ZR/ZF Outdoor Sound Power Levels

Size

(Tons)

Sound Rating

1

dB (A)

Sound Power, dB (10

-12

) Watts

Octave Band Centerline Frequency (Hz)

63

125

250

500

1000

2000

4000

8000

180 (15)

92

90

93

91

89

86

83

80

75

210 (17.5)

92

91

94

92

89

86

83

81

76

240 (20)

92

91

94

92

89

87

83

81

76

300 (25)

92

92

95

93

89

87

84

81

77

1. Rated in accordance with ARI 270 standard.