Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO.

YZE02411

INDOOR COIL MODEL NO.

FC/MC36B + MV12B

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

550

600

650

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

57

62

62

67

72

57

65

T.C.

19.5 30.3 25.6 25.2 19.8 20.4 31.2 26.6 26.2 20.0 21.4 32.2 27.6 27.1 20.3

S.C.

18.0 3.2 3.2 3.3 3.3 18.8 3.3 3.2 3.3 3.3 19.7 3.3 3.2 3.3 3.3

K.W.

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.1 1.1 1.1 1.0 1.0

75

T.C.

18.6 19.2 18.4 20.8 22.6 19.5 19.7 18.8 21.2 23.2 20.3 20.3 19.2 21.5 23.7

S.C.

17.1 16.7 13.7 14.1 11.1 17.9 17.7 14.5 14.8 11.7 18.6 18.6 15.2 15.5 12.4

K.W.

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.2 1.2 1.2 1.1 1.1

85

T.C.

17.7 18.1 17.4 19.6 21.3 18.5 18.5 17.9 19.9 21.6 19.3 19.0 18.4 20.2 22.0

S.C.

16.2 16.0 13.2 13.6 10.7 16.9 16.9 13.9 14.1 11.3 17.6 17.8 14.6 14.7 11.8

K.W.

1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2

95

T.C.

16.9 17.0 16.4 18.3 20.0 17.6 17.4 16.7 18.6 20.3 18.4 17.9 17.1 18.9 20.5

S.C.

15.3 15.3 12.6 13.0 10.3 16.0 16.1 13.3 13.6 10.8 16.7 17.0 14.0 14.2 11.3

K.W.

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

105

T.C.

16.1 16.0 15.2 17.1 18.6 16.8 16.4 15.5 17.4 18.8 17.5 16.8 15.9 17.6 19.0

S.C.

14.6 14.8 12.1 12.5 9.9 15.2 15.5 12.7 13.1 10.3 15.8 16.2 13.4 13.7 10.7

K.W.

1.8 1.7 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

115

T.C.

15.4 15.0 14.0 15.9 17.2 16.0 15.3 14.3 16.1 17.4 16.7 15.7 14.7 16.4 17.6

S.C.

13.8 14.3 11.6 12.1 9.4 14.4 14.8 12.2 12.6 9.8 14.9 15.4 12.8 13.2 10.2

K.W.

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 2.0 2.0 2.0 2.0 1.9

125

T.C.

14.7 13.9 12.8 14.7 15.8 15.3 14.3 13.1 14.9 16.0 15.8 14.6 13.4 15.1 16.2

S.C.

13.1 13.7 11.0 11.6 9.0 13.6 14.2 11.6 12.2 9.4 14.1 14.6 12.2 12.7 9.7

K.W.

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

AV24

1.01 1.00 1.00

AV36

1.01 1.00 1.00

MV12B FC/MC30B 0.97

1.06

1.00

MV12B FC/MC35B 0.97

1.06

1.00

MV12B FC/MC36B 1.00

1.00

1.00

MV12B FC/MC42B 0.97

1.06

1.00

MV16C FC/MC35C 1.00

1.00

1.00

MV16C FC/MC42C 1.00

1.00

1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*A12

FC/MC/PC30A

0.99 1.06 1.01

PV9*A12

FC/MC/PC30A

0.99 1.06 1.01

P(C,V)9*B12

FC/MC/PC30B

0.99 1.06 1.01

PV9*A12

FC/MC/PC32A

0.99 1.06 1.01

P(C,V)9*B12

FC/MC/PC35B

0.99 1.06 1.01

PV8*A12

FC/MC/PC36A

0.94 0.85 0.92

PV9*A12

FC/MC/PC36A

0.99 1.01 0.99

P(C,V)9*B12

FC/MC/PC36B

0.99 1.01 0.99

P(C,V)9*B12

FC/MC/PC42B

0.96 0.99 0.98

P(C,V)9*B12

HC30

0.96 0.99 0.98

P(C,V)9*B12

HC36

0.99 1.01 0.99

P(C,V)9*B12

HD36

0.99 1.01 0.99

PV8*A12

UC30A

0.96 0.99 0.98

P(C,V)9*B12

UC30B

0.96 0.99 0.98

PV8*A12

UC36A

0.99 1.01 0.99

P(C,V)9*B12

UC36B

0.99 1.01 0.99

P(C,V)9*B12

UC42B

0.99 1.01 0.99