COOLING CAPACITY - With Air Handler Coils

UNIT MODEL

AIR HANDLER

COIL

1

MODEL

COOLING

MODEL

W

STAGE

RATED

CFM

NET

MBH

SENSIBL

E

SEER

EER

YZE02411

AV24 17

1 535

18.6

13.6

15.00

13.00

2 800

24.0

18.6

12.50

AV36 17

1 535

18.6

13.6

15.00

13.00

2 800

24.0

18.6

12.50

MV12B 17 FC/MC30B

1 620

18.6

13.6

14.25

12.00

2 800

24.0

18.6

11.50

MV12B 17 FC/MC35B

1 650

18.1

14.4

15.00

12.15

2 775

24.0

19.6

12.00

MV16C 21 FC/MC35C

1 650

18.6

13.6

15.00

13.00

2 775

24.0

18.6

12.50

MV12B 17 FC/MC36B

1 620

18.6

13.6

15.00

11.50

2 800

24.6

18.6

12.00

MV12B 17 FC/MC42B

1 650

18.1

14.4

15.00

12.15

2 775

23.6

19.6

12.00

MV16C 21 FC/MC42C

1 650

18.6

13.6

15.00

13.00

2 775

24.0

18.6

12.50

YZE03611

AV36 17

1 830

25.0

17.5

15.75

12.70

2 1200

35.4

24.2

12.00

AV48 24

1 830

25.0

17.5

15.75

12.70

2 1200

35.4

24.2

12.00

MV12B 17 FC/MC35B

1 775

24.4

17.2

14.75

12.55

2 1200

34.0

23.9

11.50

MV12B 17 FC/MC42B

1 775

24.4

17.2

14.75

12.55

2 1200

34.0

23.9

11.50

MV16C 21 FC/MC48C

1 775

25.0

17.5

15.00

12.85

2 1200

35.4

24.2

12.00

MV12D

24 FC/MC48D

1 775

24.8

17.5

15.75

12.70

2 1200

35.4

24.2

12.00

YZE04811

AV48 24

1 1135

33.2

23.5

15.00

13.30

2 1600

45.0

32.8

12.50

AV/SV*60 24

1 1135

33.2

23.5

15.00

13.30

2 1600

45.0

32.8

12.50

F*FV060 24

1 1000

33.2

23.5

15.50

13.10

2 1600

46.0

32.8

12.15

MV20D 24 FC/MC60D

1 1000

33.2

23.5

15.50

13.05

2 1600

46.0

34.4

12.00

MV20D 24 FC/MC62D

1 1000

33.4

23.7

15.50

13.20

2 1600

47.0

34.7

12.00

YZE06011

AV60 24

1 1145

38.5

27.0

13.50

11.55

2 1800

53.5

38.5

10.25

F*FV060 24

1 1200

38.0

27.0

13.75

11.55

2 1900

53.0

38.5

10.20

MV20D 24 FC/MC60D

1 1200

38.0

27.0

13.75

11.50

2 1900

53.0

38.5

11.00

MV20D 24 FC/MC62D

1 1175

38.0

26.9

14.00

11.65

2 1800

54.0

38.9

10.40

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8

0°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.