All sensible capacity – York DNH018 User Manual

Page 12

Advertising
background image

036-21233-002-A-0903

12

Unitary Products Group

TABLE 7: DNH042 COOLING CAPACITIES - 3-1/2 TON

TEMPERATURE

OF AIR ON

CONDENSER COIL

AIR ON EVAPORATOR COIL

1,050 CFM

1,225 CFM

1,400 CFM

1,575 CFM

1,750 CFM

WB °F

WB °F

WB °F

WB °F

WB °F

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

85 °F

NET CAP.

MBH

38.6

38.4

34.0

33.3

42.1

41.8

37.0

36.3

45.5

45.3

40.1

39.2

45.3

45.0

39.9

39.1

45.1

44.8

39.7

38.9

TOTAL POWER

INPUT kW

4.05

3.83

3.95

3.91

4.01

3.79

3.92

3.87

3.98

3.76

3.88

3.84

4.12

3.90

4.02

3.98

4.27

4.03

4.16

4.12

Se

n

s

ib

le

Ca

p

a

city

MB

H

1

E

n

ter

ing D

ry

Bu

lb

°

F

86

25.5

32.6

34.0

33.3

28.9

36.8

37.0

36.3

32.2

41.0

40.1

39.2

34.4

42.9

39.9

39.1

36.6

44.8

39.7

38.9

83

22.5

29.6

34.0

33.3

25.4

33.3

37.0

36.3

28.2

36.9

40.1

39.2

29.8

38.9

39.9

39.1

31.4

40.9

39.7

38.9

80

19.6

26.6

31.9

31.9

21.8

29.7

35.6

35.6

24.1

32.8

39.3

39.2

25.1

34.3

39.5

39.1

26.2

35.7

39.7

38.9

77

16.6

23.6

28.9

28.9

18.3

26.2

32.1

32.0

20.0

28.7

35.2

35.2

20.5

29.6

34.8

34.4

21.0

30.5

34.5

33.6

74

13.6

20.7

25.9

25.9

14.7

22.7

28.5

28.5

15.9

24.7

31.1

31.1

15.8

25.0

30.2

29.8

15.8

25.3

29.2

28.4

71

-

17.7

22.9

22.9

-

19.1

25.0

24.9

-

20.6

27.1

27.0

-

20.3

25.5

25.1

-

20.1

24.0

23.2

68

-

14.7

19.9

19.9

-

15.6

21.5

21.4

-

16.5

23.0

22.9

-

15.7

20.9

20.5

-

14.9

18.8

18.0

105 °F

NET CAP.

MBH

36.8

36.2

32.1

31.6

40.2

39.5

35.1

34.5

43.6

42.9

38.1

37.5

43.4

42.7

37.9

37.3

43.3

42.6

37.8

37.2

TOTAL POWER

INPUT kW

4.45

4.20

4.29

4.28

4.41

4.17

4.25

4.24

4.37

4.13

4.21

4.20

4.51

4.26

4.34

4.33

4.65

4.39

4.48

4.46

S

e

nsi

b

le

C

apaci

ty

MB

H

1

En

te

ri

n

g

Dr

y

Bu

lb

°

F

86

25.5

32.1

32.1

31.6

28.9

36.2

35.1

34.5

32.2

40.4

38.1

37.5

34.6

41.5

37.9

37.3

36.9

42.6

37.8

37.2

83

22.5

29.1

32.1

31.6

25.3

32.7

35.1

34.5

28.1

36.3

38.1

37.5

29.9

38.5

37.9

37.3

31.7

40.7

37.8

37.2

80

19.5

26.1

30.6

30.4

21.8

29.2

34.2

33.9

24.1

32.2

37.8

37.5

25.3

33.8

37.8

37.3

26.5

35.4

37.8

37.2

77

16.5

23.1

27.7

27.4

18.3

25.6

30.7

30.4

20.0

28.1

33.7

33.4

20.6

29.2

33.1

32.7

21.3

30.2

32.6

32.0

74

13.5

20.1

24.7

24.4

14.7

22.1

27.1

26.8

15.9

24.0

29.6

29.3

16.0

24.5

28.5

28.0

16.1

25.0

27.4

26.8

71

-

17.1

21.7

21.4

-

18.5

23.6

23.3

-

19.9

25.5

25.2

-

19.9

23.8

23.4

-

19.8

22.2

21.6

68

-

14.1

18.7

18.4

-

15.0

20.1

19.8

-

15.9

21.5

21.1

-

15.2

19.2

18.7

-

14.6

16.9

16.3

115 °F

NET CAP.

MBH

35.4

33.7

29.9

29.5

38.7

36.8

32.7

32.2

42.1

40.0

35.5

35.0

41.8

39.7

35.2

34.8

41.4

39.4

35.0

34.5

TOTAL POWER

INPUT kW

4.80

4.64

4.73

4.72

4.78

4.62

4.71

4.70

4.75

4.59

4.68

4.67

4.88

4.71

4.80

4.80

5.00

4.83

4.93

4.92

S

e

n

s

ib

le

C

apaci

ty

MB

H

1

E

n

te

ring

Dry

Bu

lb

°

F

86

24.8

31.0

29.9

29.5

28.2

34.9

32.7

32.2

31.6

38.7

35.5

35.0

34.0

39.1

36.2

34.8

36.3

39.4

35.0

34.5

83

21.8

28.0

29.9

29.5

24.7

31.6

32.7

32.2

27.5

35.3

35.5

35.0

29.3

36.8

35.2

34.8

31.1

38.4

35.0

34.5

80

18.8

25.0

28.4

28.1

21.1

28.1

31.9

31.6

23.5

31.2

35.4

35.0

24.7

32.8

35.2

34.8

25.9

34.4

35.0

34.5

77

15.8

22.0

25.4

25.1

17.6

24.6

28.3

28.0

19.4

27.1

31.3

30.9

20.0

28.2

30.5

30.1

20.7

29.2

29.7

29.3

74

12.8

19.0

22.4

22.1

14.1

21.0

24.8

24.5

15.3

23.0

27.2

26.9

15.4

23.5

25.9

25.5

15.5

24.0

24.5

24.1

71

-

16.0

19.4

19.1

-

17.5

21.3

21.0

-

18.9

23.1

22.8

-

18.9

21.2

20.8

-

18.8

19.3

18.8

68

-

13.1

16.4

16.1

-

14.0

17.7

17.4

-

14.9

19.0

18.7

-

14.2

16.6

16.2

-

13.6

14.1

13.6

125 °F

NET CAP.

MBH

34.0

31.1

27.6

27.3

37.3

34.1

30.3

30.0

40.6

37.1

32.9

32.6

40.1

36.6

32.5

32.2

39.6

36.2

32.1

31.8

TOTAL POWER

INPUT kW

5.16

5.08

5.18

5.17

5.14

5.07

5.16

5.16

5.13

5.05

5.15

5.14

5.24

5.17

5.26

5.26

5.36

5.28

5.38

5.37

Se

n

s

ib

le

Ca

p

a

city

MB

H

1

E

n

ter

ing D

ry

Bu

lb

°

F

86

24.1

29.9

27.6

27.3

27.6

33.5

30.3

30.0

31.0

37.1

32.9

32.6

33.4

36.6

32.5

32.2

35.7

36.2

32.1

31.8

83

21.1

26.9

27.6

27.3

24.0

30.6

30.3

30.0

26.9

34.3

32.9

32.6

28.7

35.2

32.5

32.2

30.5

36.2

32.1

31.8

80

18.1

23.9

26.1

25.9

20.5

27.1

29.5

29.2

22.8

30.2

32.9

32.6

24.1

31.8

32.5

32.2

25.3

33.4

32.1

31.8

77

15.1

21.0

23.1

22.9

17.0

23.5

26.0

25.7

18.8

26.1

28.8

28.5

19.4

27.2

27.9

27.5

20.1

28.2

26.9

26.6

74

12.1

18.0

20.1

19.9

13.4

20.0

22.5

22.2

14.7

22.0

24.8

24.4

14.8

22.5

23.2

22.9

14.9

23.0

21.7

21.3

71

-

15.0

17.2

16.9

-

16.4

18.9

18.6

-

17.9

20.7

20.3

-

17.9

18.6

18.2

-

17.8

16.5

16.1

68

-

12.0

14.2

13.9

-

12.9

15.4

15.1

-

13.8

16.6

16.3

-

13.2

13.9

13.6

-

12.6

11.2

10.9

125 °F

NET CAP.

MBH

32.7

28.6

25.4

25.2

35.9

31.4

27.9

27.7

39.1

34.2

30.4

30.2

38.4

33.6

29.8

29.6

37.7

33.0

29.2

29.1

TOTAL POWER

INPUT kW

5.50

5.50

5.60

5.60

5.50

5.50

5.60

5.60

5.50

5.50

5.60

5.60

5.60

5.60

5.70

5.70

5.70

5.70

5.80

5.80

S

e

nsi

b

le

C

apaci

ty

MB

H

1

En

te

ri

n

g

Dr

y

Bu

lb

°

F

86

23.4

28.9

25.4

25.2

26.9

32.2

27.9

27.7

30.4

35.5

30.4

30.2

32.8

34.2

29.8

29.6

35.2

33.0

29.2

29.1.

83

20.4

25.9

25.4

25.2

23.4

29.6

27.9

27.7

26.3

33.3

30.4

30.2

28.1

33.6

29.8

29.6

29.9

33.9

29.2

29.1

80

17.4

22.9

23.9

23.6

19.8

26.0

27.2

26.9

22.2

29.2

30.5

30.2

23.5

30.8

29.9

29.6

24.7

32.4

29.2

29.1

77

14.4

19.9

20.9

20.6

16.3

22.5

23.7

23.3

18.2

25.1

26.4

26.1

18.8

26.2

25.2

25.0

19.5

27.2

24.0

23.8

74

11.5

16.9

17.9

17.6

12.8

18.9

20.1

19.8

14.1

21.0

22.3

22.0

14.2

21.5

20.6

20.3

14.3

22.0

18.8

18.6

71

-

13.9

14.9

14.6

-

15.4

16.6

16.3

-

16.9

18.3

17.9

-

16.9

15.9

15.7

-

16.8

13.6

13.4

68

-

10.9

11.9

11.6

-

11.9

13.0

12.7

-

12.8

14.2

13.8

-

12.2

11.3

11.0

-

11.6

8.4

8.2

1.

These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY