Table 2: ratings cooling/gas heating – York DNH018 User Manual

Page 7

Advertising
background image

036-21233-002-A-0903

Unitary Products Group

7

TABLE 2: RATINGS COOLING/GAS HEATING

MODEL

DNH

NET COOLING CAPACITY

1

SOUND

RATING

(dbels)

2

GAS HEAT CAPACITY / EFFICIENCIES

MBH

SEER

3

INPUT
(MBH)

OUTPUT

(MBH)

AFUE

4

(%)

NUMBER OF

BURNERS

TEMP.

RISE

(°F) RANGE

018N03606

17.4

12.0

80

45

36

80.2

2

25 - 55

024N03606

23.8

12.4

81

45

36

80.2

2

25 - 55

024N05606

23.8

12.4

81

70

56

80.2

3

30 - 60

030N03606

28.0

12.0

80

45

36

80.2

2

25 - 55

030N03625

28.0

12.0

80

45

36

80.2

2

25 - 55

030N03646

28.0

12.0

80

45

36

80.2

2

25 - 55

030N05606

28.0

12.0

80

70

56

80.2

3

30 - 60

030N05625

28.0

12.0

80

70

56

80.2

3

30 - 60

030N05646

28.0

12.0

80

70

56

80.2

3

30 - 60

036N03606

36.0

12.0

81

45

36

80.4

2

25 - 55

036N03625

36.0

12.0

81

45

36

80.4

2

25 - 55

036N03646

36.0

12.0

81

45

36

80.4

2

25 - 55

036N03658

36.0

12.0

81

45

36

80.4

2

25 - 55

036N05606

36.0

12.0

81

70

56

80.2

3

25 - 55

036N05625

36.0

12.0

81

70

56

80.2

3

25 - 55

036N05646

36.0

12.0

81

70

56

80.2

3

25 - 55

036N05658

36.0

12.0

81

70

56

80.2

3

25 - 55

036N07206

36.0

12.0

81

90

72

80.1

4

30 - 60

036N07225

36.0

12.0

81

90

72

80.1

4

30 - 60

036N07246

36.0

12.0

81

90

72

80.1

4

30 - 60

036N07258

36.0

12.0

81

90

72

80.1

4

30 - 60

042N06506

42.0

12.0

80

80

64

80.6

3

25 - 55

042N06525

42.0

12.0

80

80

64

80.6

3

25 - 55

042N06546

42.0

12.0

80

80

64

80.6

3

25 - 55

042N06558

42.0

12.0

80

80

64

80.6

3

25 - 55

042N09006

42.0

12.0

80

108

87

80.8

4

45 - 75

042N09025

42.0

12.0

80

108

87

80.8

4

45 - 75

042N09046

42.0

12.0

80

108

87

80.8

4

45 - 75

042N09058

42.0

12.0

80

108

87

80.8

4

45 - 75

048N06506

48.0

12.0

84

80

64

80.8

3

25 - 55

048N06525

48.0

12.0

84

80

64

80.8

3

25 - 55

048N06546

48.0

12.0

84

80

64

80.8

3

25 - 55

048N06558

48.0

12.0

84

80

64

80.8

3

25 - 55

048N09006

48.0

12.0

84

108

86

80.6

4

35 - 65

048N09025

48.0

12.0

84

108

86

80.6

4

35 - 65

048N09046

48.0

12.0

84

108

86

80.6

4

35 - 65

048N09058

48.0

12.0

84

108

86

80.6

4

35 - 65

048N11006

48.0

12.0

84

135

107

80.5

5

45 - 75

048N11025

48.0

12.0

84

135

107

80.5

5

45 - 75

048N11046

48.0

12.0

84

135

107

80.5

5

45 - 75

048N11058

48.0

12.0

84

135

107

80.5

5

45 - 75

060N06506

59.0

12.0

84

80

64

80.7

3

25 - 55

060N06525

59.0

12.0

84

80

64

80.7

3

25 - 55

060N06546

59.0

12.0

84

80

64

80.7

3

25 - 55

060N06558

59.0

11.0

84

80

64

80.7

3

25 - 55

060N09006

59.0

12.0

84

108

87

80.9

4

35 - 65

060N09025

59.0

12.0

84

108

87

80.9

4

35 - 65

060N09046

59.0

12.0

84

108

87

80.9

4

35 - 65

060N09058

59.0

11.0

84

108

87

80.9

4

35 - 65

060N11006

59.0

12.0

84

135

107

80.2

5

45 - 75

060N11025

59.0

12.0

84

135

107

80.2

5

45 - 75

060N11046

59.0

12.0

84

135

107

80.2

5

45 - 75

060N11058

59.0

11.0

84

135

107

80.2

5

45 - 75

1.

Net Cooling Capacity = ARI 210 standard rating conditions.

2.

(dbels) = ARI 270-95

3.

Seasonal Energy Efficiency Ration - the total cooling output in BTU’s during a normal annual usage period for cooling divided by
the total electric power input in watt-hours during the same period.

4.

AFUE = Annual Fuel Utilization Efficiency.

Advertising