15 supply air blower performance (bp072, Belt drive) - bottom duct application – York BP 036 User Manual

Page 22

Advertising
background image

255027-YTG-B-0507

22

Unitary Products Group

TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (BP072 BELT DRIVE) - BOTTOM DUCT APPLICATION

AIR

FLOW

CFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG

1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1500

-

-

-

-

-

-

-

-

-

923

639

0.69 956

702

0.75 990

766

0.82 1024

830

0.89

1600

-

-

-

-

-

-

924

684

0.73 956

742

0.80 988

805

0.86 1022

870

0.93 1057

933

1.00

1700

-

-

-

927

736

0.79 957

788

0.84 988

846

0.91 1021

909

0.97 1055

973

1.04 1089 1037

1.11

1800 930

798

0.86 959

840

0.90 989

891

0.96 1021

950

1.02 1054 1013

1.09 1087 1077

1.16 1122 1141

1.22

1900 963

902

0.97 992

944

1.01 1022

996

1.07 1053 1054

1.13 1086 1117

1.20 1120 1181

1.27 1155 1245

1.34

2000 995

1007

1.08 1024 1049

1.13 1054 1101

1.18 1086 1159

1.24 1118 1222

1.31 1152 1287

1.38 1187 1350

1.45

2100 1028 1113

1.19 1056 1155

1.24 1086 1207

1.29 1118 1265

1.36 1151 1328

1.42 1184 1393

1.49 1219 1456

1.56

2200 1060 1221

1.31 1088 1262

1.35 1119 1314

1.41 1150 1372

1.47 1183 1435

1.54 1217 1500

1.61

-

-

-

2300 1091 1329

1.43 1120 1371

1.47 1150 1422

1.53 1182 1481

1.59 1215 1544

1.66

-

-

-

-

-

-

2400 1123 1439

1.54 1152 1480

1.59 1182 1532

1.64 1214 1590

1.71

-

-

-

-

-

-

-

-

-

2500 1155 1549

1.66 1183 1591

1.71

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2600

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2700

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2800

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

AIR

FLOW

CFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG

1

0.9

1.0

1.1

1.2

1.3

1.4

1.5

RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1500 1060

890

0.95 1096

944

1.01 1133

989

1.06 1170 1022

1.10 1208 1042

1.12 1246 1044

1.12

-

-

-

1600 1092

993

1.07 1129 1047

1.12 1165 1092

1.17 1203 1126

1.21 1240 1145

1.23

-

-

-

-

-

-

1700 1125 1097

1.18 1161 1151

1.23 1198 1196

1.28 1235 1229

1.32

-

-

-

-

-

-

-

-

-

1800 1158 1201

1.29 1194 1255

1.35 1231 1300

1.39

-

-

-

-

-

-

-

-

-

-

-

-

1900 1190 1305

1.40 1226 1359

1.46

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2000 1222 1410

1.51

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2100

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2200

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2300

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2400

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2500

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2600

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2700

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2800

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK56 blower sheave and A36 belt.

Advertising