255027-YTG-B-0507

Unitary Products Group

37

FIGURE 7 -

DISCONNECT/BLOWER ACCESS LOCATION

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

CONTROL BOX
ACCESS

A,B
WIRING ENTRY
(See Detail “B”)

MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the

blower housing inside
the blower compartment)

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER MOTOR
ACCESS

FILTER
ACCESS

DOT PLUGS

TABLE 28: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO

1

Control Wiring

2

Side

Bottom

B

2” KO

1

Power Wiring

Side

Bottom

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

1. Opening in the bottom to the unit can be located by the

side in the insulation.

2. Do not remove the 2” knockout ring.

TABLE 29: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

24”

Below Unit

1

0”

Above Unit

2

72” (For

Condenser Air Discharge)

1. Units may be installed on combustible floors made

from wood or class A, B, or C roof covering material.

2. Units must be installed outdoors. Overhanging struc-

tures or shrubs should not obstruct condenser air dis-
charge outlet.