Guide specifications, General, Description – York BP 036 User Manual

Page 40: Unit cabinet, 10 roof curb dimensions

Advertising
background image

255027-YTG-B-0507

40

Unitary Products Group

GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.

York's Sunline 2000

TM

units are convertible single package

heat pumps. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Models are
available with a wide variety of factory-mounted options and
field-installed accessories to make them suitable for almost
every application. All units are self-contained and assembled
on full perimeter base rails with holes in the four corners for
overhead rigging. Every unit is completely piped, wired,
charged and tested at the factory to simplify the field installa-
tion and to provide years of dependable operation. All models
(including those with an economizer) are suitable for either bot-
tom or horizontal duct connections. Models with power exhaust
are suitable for bottom duct connections only. For bottom duct,
remove the sheet metal panels from the supply and return air
openings through the base of the unit. For horizontal duct,
remove the supply and return air panels on the rear of the unit.

All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip

for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All units
have long lasting powder paint cabinets with 1000 hour salt
spray test approval under ASTMB117 procedures. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged heat
pumps designed for outdoor mounted installation.

The 3, 4 and 5 ton units shall have a minimum SEER rating of
13.0 and a minimum HSPF rating of 7.70. The 6 ton units
shall have a minimum EER rating of 10.2. They shall have
built-in field convertible duct connections for down discharge
supply/return or horizontal discharge supply/return, and be
available with factory installed options or field installed acces-
sories. The units shall be factory wired, piped, charged with
R-22 refrigerant and factory tested prior to shipment. All unit
wiring shall be both numbered and color coded. All units the
cooling performance shall be rated in accordance with DOE
and ARI test procedures. Units shall be CSA listed, classified
to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-

FIGURE 10 - ROOF CURB DIMENSIONS

Advertising