2 rectifier bracket, 3 rectifier visual displays, 2 rectifier bracket -2 – 3Com External PoE Power System PSE2500-A3 User Manual

Page 13: 3 rectifier visual displays -2

Advertising
background image

User Manual
PSE2500-A3 External PoE
Power System

Chapter 2 System Description

2-2

2.1.2 Rectifier Bracket

Up to three rectifiers can be mounted in each system of rectifier

bracket. Each rectifier in the bracket receives AC power from the AC

distribution.

2.1.3 Rectifier Visual Displays

The front panel of the rectifier has three LEDs. Their names,

colors and meanings are as follows.

Table 2-1 LEDs state description

Condition

AC OK

(green)

DC OK

(green)

Fault

(Red)

All OK

1

1

0

Thermal alarm
(Ambient)

1 0 0

Thermal alarm (fan fail)

1

0

1

Blown AC fuse in unit

1

0

1

Low or no AC > 15mS
(single unit)

0 0 0

AC not present in any
rectifier

0 0 0

Over Voltage Latched
shutdown

1 0 1

Any internal failure

1

0

1

The Front panel of the rectifier is as follows.

Advertising