Delta 1.07 VFD-D D User Manual

Page 81

Advertising
background image

Chapter 4 Parameter Settings|DD Series


4-57

Emergency/Force Stop Deceleration Method

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 3

Settings 0:Coast to stop

1: Decelerate by 1st decel. time

2: Decelerate by 2nd decel. time

3:By Pr.05.33 setting

When multi-function input terminal (MI) is set to 09 or 11, this parameter is active and the drive will

operate as the setting in Pr.06-07.

Low Voltage Level

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 180.0

Settings 160.0~270.0Vdc

High Temperature Overheat Warning (OH)

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 85.0

Settings 0.0~110.0℃

Action after door re-open/re-close

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 2

Settings Bit0=0: Disable to detect the incorrect open/close limit function

Bit0=1: Enable to detect the incorrect open/close limit function

Bit1=0: Enable to re-open when door close error

Bit1=1: Disable to re-open when door close error

Bit2=0: Enable S-Curve when re-open

Bit2=1: Disable S-Curve when re-open

Bit3=0: Disable to reset door width to 100.0% after door open completed

Bit3=1: Enable to reset door width to 100.0% after door open completed

When Bit 0=1, if the drive is in distance control mode, it is able to detect the door open/close error; in

addition, when MO(multi-function output terminal) is set to 8, the drive will output door open/close error

warning.

In Distance Control Mode, the detection method for the incorrect door open/close limit is shown as

follows.

04-04
Door Open Final

by Speed Begins

04-06
Door Open

by Holding
Speed Begins

Door Open Limit
100.0%

05-04

Door Close
by Final Speed
Begins

05-06

Door Close
by Holding
Speed Begins

Door Close Limit

0.0%

Open(REV)

Close(FWD)

No signal
for the door
close limit

The signal for the door close limit is received

The signal for the door open limit is received

No signal

for door
open limit